Plan Review Notes
Plan Review Notes For Permit 15101067
Permit Number 15101067
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-21 11:12:531ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 THE PLAN IS REDUCED AND TOO SMALL TO READ AND TOO SMALL
 FOR RECORD RETENTION. PLEASE PROVIDE AN ENLARGED PLAN.
  
 FBC FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 THE WIND DESIGN AND STRUCTURAL ATTACHMENT INFORMATION
 IS UNCLEAR AND APPEARS GENERIC. SUCH DESIGN MUST BE
 SITE SPECIFIC. PLEASE PROVIDE THE SPECIFIC APPLICABLE
 DESIGN PRESSURES AS DETERMINED USING THE METHODS IN
 FBC-R301.1.3 ENGINEERED DESIGN. PLEASE PROVIDE A
 SPECIFIC PLAN INDICATING THE LOCATION AND TYPE OF
 CONNECTORS TO BE INSTALLED. PROVIDE WIND DESIGN
 CRITERIA FOR THE SPECIFIC GEOGRAPHICAL LOCATION OF THE
 BUILDING AND CONSIDERING THE PROPOSED LOCATION OF THE
 SYSTEM ON THE BUILDING. IF DESIGN IS NOT TO BE PROVIDED
 BY A FLORIDA LICENSED ENGINEER, THEN PROVIDE STRUCTURAL
 CALCULATIONS TO JUSTIFY THE DESIGN.
  
 NAMASTE'
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  