| Plan Review Notes For Permit 15101064 |
| Permit Number |
15101064 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2016-11-18 12:26:17 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #15101064 | | | 11/18/16 | | | | | | 1) THE NEW 5-TON RTU REQUIRES INSTALLATION OF A DUCT | | | SMOKE DETECTOR IN THE RETURN AIR SYSTEM IN COMPLIANCE | | | WITH SECTION 606.2.1. PLEASE REVISE THE PLAN TO SHOW | | | THE LOCATION OF THE DEVICE AND TEST STATION, AND | | | PROVIDE NOTES TO INDICATE THE SEQUENCE OF OPERATION. | | | | | | 2) ALL REVISED PLAN SHEETS MUST BE PERMANENTLY ATTACHED | | | INTO THE PLAN SETS AND ALL SHEETS BEING REPLACED MUST | | | BE REMOVED FROM THE SETS, VOIDED, AND RETAINED IN THE | | | PERMIT PACKAGE FOR REFERENCE ONLY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|