| 2016-04-11 12:48:25 | PLUMBING COMMENTS; |
| | |
| | 1) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS & |
| | INSTALLATION MANUAL FOR THE PEDICURE CHAIRS. WPB AMEND. |
| | TO FBC SEC. 107.2.1. 2ND REQUEST |
| | 2) THE BREAK ROOM SINK SHALL COMPLY WITH THE 2014 |
| | FBC-ACCESSIBILITY SEC. 212, 212.3. 2ND REQUEST |
| | 3) SHT. A-2 INDICATES ELEVATION 11 K11 ON SHT. A-5 FOR |
| | THE BREAKROOM ELEVATIONS. THERE IS NO ELEVATION 11 K11 |
| | ON SHT. A-5. CLARIFY. 2ND REQUEST |
| | 4) SHT. A-7 - FINISH SCHEDULE - THE WALLS IN THE MEN?S |
| | & WOMEN?S TOILET ROOMS SHALL COMPLY WITH 2014 FBC |
| | SEC.1210.2.2. 2ND REQUEST |
| | 5) WATER FOUNTAIN IS REQUIRED PER FBC PL SEC. 403.1 |
| | TABLE 403.1 WATER FOUNTAINS SHALL COMPLY WITH FBC ACC. |
| | SEC. 307 AND 602. |
| | 6) SUBMIT AN OCCUPANT LOAD FOR THIS SPACE IN ACCORDANCE |
| | WITH 2014 FBC TABLE 1004.1.2. 2ND REQUEST |
| | 7) INDICATE ON THE PLAN WHAT TYPE OF |
| | PRODUCTS/PREPARATION WILL BE DONE AT THE JUICE BAR .WPB |
| | AMEND . TO FBC SEC. 107 .2.1. 2ND REQUEST |
| | 8) A SERVICE SINK IS REQUIRED PER FBC PL SEC. 403.1 |
| | TABLE 403.1 |
| | 9) THE VENTING FOR PEDICURE CHAIRS SHALL COMPLY WITH |
| | FBC PL SEC. 914.2 VENT CONNECTION. |
| | THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN |
| | THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL |
| | CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED |
| | IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE |
| | SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. |
| | |
| | IT APPEARS THAT ONLY THE NEW MEP PAGES WERE RESUBMITED |
| | PLEASE CLARIFY |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |