Plan Review Notes
Plan Review Notes For Permit 15101064
Permit Number 15101064
Review Stop P
Sequence Number 3
Notes
Date Text
2016-04-11 12:48:25PLUMBING COMMENTS;
  
 1) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS &
 INSTALLATION MANUAL FOR THE PEDICURE CHAIRS. WPB AMEND.
 TO FBC SEC. 107.2.1. 2ND REQUEST
 2) THE BREAK ROOM SINK SHALL COMPLY WITH THE 2014
 FBC-ACCESSIBILITY SEC. 212, 212.3. 2ND REQUEST
 3) SHT. A-2 INDICATES ELEVATION 11 K11 ON SHT. A-5 FOR
 THE BREAKROOM ELEVATIONS. THERE IS NO ELEVATION 11 K11
 ON SHT. A-5. CLARIFY. 2ND REQUEST
 4) SHT. A-7 - FINISH SCHEDULE - THE WALLS IN THE MEN?S
 & WOMEN?S TOILET ROOMS SHALL COMPLY WITH 2014 FBC
 SEC.1210.2.2. 2ND REQUEST
 5) WATER FOUNTAIN IS REQUIRED PER FBC PL SEC. 403.1
 TABLE 403.1 WATER FOUNTAINS SHALL COMPLY WITH FBC ACC.
 SEC. 307 AND 602.
 6) SUBMIT AN OCCUPANT LOAD FOR THIS SPACE IN ACCORDANCE
 WITH 2014 FBC TABLE 1004.1.2. 2ND REQUEST
 7) INDICATE ON THE PLAN WHAT TYPE OF
 PRODUCTS/PREPARATION WILL BE DONE AT THE JUICE BAR .WPB
 AMEND . TO FBC SEC. 107 .2.1. 2ND REQUEST
 8) A SERVICE SINK IS REQUIRED PER FBC PL SEC. 403.1
 TABLE 403.1
 9) THE VENTING FOR PEDICURE CHAIRS SHALL COMPLY WITH
 FBC PL SEC. 914.2 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE.
  
 IT APPEARS THAT ONLY THE NEW MEP PAGES WERE RESUBMITED
 PLEASE CLARIFY
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  