| 2016-03-28 08:49:28 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #151201064 | | | 3/28/16 | | | | | | 1) PROVIDE DRAWINGS AND DETAILS FOR THE NEW EXHAUST | | | SYSTEMS INDICATING THE LOCATIONS OF THE EXHAUST INLETS, | | | GRILL SIZES, GAGE OF METAL EXHAUST DUCT, AND FAN | | | SCHEDULES. PLEASE NOTE THAT THE ARCHITECTURAL PLANS | | | NEED TO BE REVISDED TO SHOW THE LOCATIONS OF, AND | | | CONSTRUCTION DETAILS FOR THE NEW KNEE WALLS AT THE NAIL | | | STATIONS. | | | 2) PROVIDE AN AIR BALANCE CALCULATION, AND A SEQUENCE | | | OF OPERATION FOR THE EXHAUST SYSTEM. | | | 3) PROVIDE A MECHANIOCAL ROOF PLAN INDICATING THE | | | LOCATIONS OF ALL ROOF TOP EQUIPMENT: SHOW CLEARANCE | | | DISTANCE MEASUREMENTS FOR AIR INTAKES TO EXHAUST AND | | | VENT OUTLETS, EQUIPMENT CLEARANC DISTANCES TO RROF | | | EDGES, AND THE NEW RTU CONDENSATE PIPING RUN. | | | 4) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR | | | INSTALLATION OF THE RTU, AND PROVIDE DETAILS FOR | | | INSTALLATION OF THE NEW EXHAUST FANS. PLEASE SUBMIT | | | MIAMI-DADE NOA'S AND/OR FL. PRODUCT APPROVALS FOR THE | | | FANS AND CURBS WITH APPROVAL SIGNATURES BY THE ENGINEER | | | OF RECORD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|