Plan Review Notes
Plan Review Notes For Permit 15101064
Permit Number 15101064
Review Stop M
Sequence Number 3
Notes
Date Text
2016-03-28 08:49:283RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #151201064
 3/28/16
  
 1) PROVIDE DRAWINGS AND DETAILS FOR THE NEW EXHAUST
 SYSTEMS INDICATING THE LOCATIONS OF THE EXHAUST INLETS,
 GRILL SIZES, GAGE OF METAL EXHAUST DUCT, AND FAN
 SCHEDULES. PLEASE NOTE THAT THE ARCHITECTURAL PLANS
 NEED TO BE REVISDED TO SHOW THE LOCATIONS OF, AND
 CONSTRUCTION DETAILS FOR THE NEW KNEE WALLS AT THE NAIL
 STATIONS.
 2) PROVIDE AN AIR BALANCE CALCULATION, AND A SEQUENCE
 OF OPERATION FOR THE EXHAUST SYSTEM.
 3) PROVIDE A MECHANIOCAL ROOF PLAN INDICATING THE
 LOCATIONS OF ALL ROOF TOP EQUIPMENT: SHOW CLEARANCE
 DISTANCE MEASUREMENTS FOR AIR INTAKES TO EXHAUST AND
 VENT OUTLETS, EQUIPMENT CLEARANC DISTANCES TO RROF
 EDGES, AND THE NEW RTU CONDENSATE PIPING RUN.
 4) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE RTU, AND PROVIDE DETAILS FOR
 INSTALLATION OF THE NEW EXHAUST FANS. PLEASE SUBMIT
 MIAMI-DADE NOA'S AND/OR FL. PRODUCT APPROVALS FOR THE
 FANS AND CURBS WITH APPROVAL SIGNATURES BY THE ENGINEER
 OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  