| 2016-03-02 19:15:17 | JOB PERMIT NUMBER: 15101064 |
| | JOB ADDRESS: 112 N DIXIE HIGHWAY |
| | WEST PALM BEACH |
| | DATE: MARCH 2 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | - RISER DIAGRAM TO INCLUDE MAIN DISCONNECTING OF |
| | SERVICE & FEEDER CONDUCTORS, AIC RATING OF ELECTRICAL |
| | EQUIPMENT AND OCPD, GROUNDING DETAIL TO INCLUDE |
| | GROUNDING ELECTRODE CONDUCTOR SIZE , FURTHER MORE |
| | INTERSYSTEM BONDING REQUIRED. NEC 230.70 , 250.66 & 94 |
| | , 215.5 , 110.9 & 10 |
| | - ARC FLASH HAZARD WARNING LABEL REQUIRED AS WELL AS |
| | AVAILABLE FAULT CURRENT MARKING. NEC 110.16, 110.24 |
| | - PROVIDE DISCONNECTS ON FLOOR PLAN FOR W/H & A/C |
| | EQUIPMENT WITHIN SIGHT. WBA 107. A SERVICE RECEPTACLE |
| | IS REQUIRED BY MECHANICAL UNIT FOR MAINTENANCE PURPOSES |
| | NEC 210.63 |
| | - GFCI PROTECTION WITHIN 6 FT OF SINKS AND ALL KITCHEN |
| | COUNTERTOPS IN OTHER THAN DWELLING UNITS NEC 210.8 B. |
| | IN ADDITION MAKE SURE DRINKING FOUNTAIN IS ALSO GFCI |
| | PROTECTED NEC 422.52 |
| | - PROVIDE SHOW WINDOW OUTLETS PER NEC 210.62 AS WELL |
| | AS DEDICATED SIGN CIRCUIT PER NEC 600.5 |
| | - ALL ELECTRICAL APPARATUS SHALL BE PROPERLY MARKED AS |
| | TO INDICATE WERE IN THE BUILDING IS THE SOURCE OF |
| | SUPPLY AT ALL LOCATIONS IN THE SYSTEM. NEC 408.4 B |
| | - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED |
| | BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE |
| | LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON |
| | OWN CIRCUIT. |
| | - FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A |
| | BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION |
| | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER |
| | CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING |
| | POWER DENSITY CHART TO SHOW COMPLIANCE. |
| | - COMPLY WITH FBC ? E C 405 FOR OCCUPANCY SENSORS IN |
| | BATHROOMS, DAYLIGHT ZONE CONTROLS BY FRONT WINDOWS , |
| | DIMMER CONTROLS OR TANDEM WIRING LIGHTING REDUCTION TO |
| | 50 %, TO ADD A FIXTURE SCHEDULE WITH MOUNTING DETAIL |
| | SHALL BE PROVIDED. |
| | |
| | |
| | |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |