2016-03-02 19:15:17JOB PERMIT NUMBER: 15101064
 JOB ADDRESS: 112 N DIXIE HIGHWAY
 WEST PALM BEACH
 DATE: MARCH 2 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 - RISER DIAGRAM TO INCLUDE MAIN DISCONNECTING OF
 SERVICE & FEEDER CONDUCTORS, AIC RATING OF ELECTRICAL
 EQUIPMENT AND OCPD, GROUNDING DETAIL TO INCLUDE
 GROUNDING ELECTRODE CONDUCTOR SIZE , FURTHER MORE
 INTERSYSTEM BONDING REQUIRED. NEC 230.70 , 250.66 & 94
 , 215.5 , 110.9 & 10
 - ARC FLASH HAZARD WARNING LABEL REQUIRED AS WELL AS
 AVAILABLE FAULT CURRENT MARKING. NEC 110.16, 110.24
 - PROVIDE DISCONNECTS ON FLOOR PLAN FOR W/H & A/C
 EQUIPMENT WITHIN SIGHT. WBA 107. A SERVICE RECEPTACLE
 IS REQUIRED BY MECHANICAL UNIT FOR MAINTENANCE PURPOSES
 NEC 210.63
 - GFCI PROTECTION WITHIN 6 FT OF SINKS AND ALL KITCHEN
 COUNTERTOPS IN OTHER THAN DWELLING UNITS NEC 210.8 B.
 IN ADDITION MAKE SURE DRINKING FOUNTAIN IS ALSO GFCI
 PROTECTED NEC 422.52
 - PROVIDE SHOW WINDOW OUTLETS PER NEC 210.62 AS WELL
 AS DEDICATED SIGN CIRCUIT PER NEC 600.5
 - ALL ELECTRICAL APPARATUS SHALL BE PROPERLY MARKED AS
 TO INDICATE WERE IN THE BUILDING IS THE SOURCE OF
 SUPPLY AT ALL LOCATIONS IN THE SYSTEM. NEC 408.4 B
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 - FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A
 BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
 - COMPLY WITH FBC ? E C 405 FOR OCCUPANCY SENSORS IN
 BATHROOMS, DAYLIGHT ZONE CONTROLS BY FRONT WINDOWS ,
 DIMMER CONTROLS OR TANDEM WIRING LIGHTING REDUCTION TO
 50 %, TO ADD A FIXTURE SCHEDULE WITH MOUNTING DETAIL
 SHALL BE PROVIDED.
  
  
  
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  