| Plan Review Notes For Permit 15101064 |
| Permit Number |
15101064 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-05 10:44:44 | 1) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS & | | | INSTALLATION MANUAL FOR THE PEDICURE CHAIRS. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 2) THE BREAK ROOM SINK SHALL CCOMPLY WITH THE 2014 | | | FBC-ACCESSIBILITY SEC. 212, 212.3. | | | 3) SHT. A-2 INDICATES ELEVATION "K" ON SHT. A-5 FOR THE | | | BREAKROOM ELEVATIONS. THERE IS NO ELEVATION "K" ON SHT. | | | A-5. CLARIFY. | | | 4) SHT. A-7 - FINISH SCHEDULE - THE WALLS IN THE MEN'S | | | & WOMEN'S TOILET ROOMS SHALL COMPLY WITH 2014 FBC | | | SEC.1210.2.2. | | | 5) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR | | | REVIEW.SHOW ALL PIPE SIZES ON THE RISER DIAGRAMS.WPB | | | AMEND. TO FBC SEC. 107.3.5.1.3. | | | 6) SUBMIT AN OCCUPANT LOAD FOR THIS SPACE IN ACCORDANCE | | | WITH 2014 FBC TABLE 1004.1.2. | | | 7) INDICATE ON THE PLAN WHAT TYPE OF | | | PRODUCTS/PREPARATION WILL BE DONE AT THE JUICE BAR.WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|