| Plan Review Notes For Permit 15101064 |
| Permit Number |
15101064 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-06 13:05:40 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15101064 | | | 11/6/15 | | | | | | 1) NO MECHANICAL PLANS WERE INCLUDED WITH THE SUBMITTED | | | PLAN SETS FOR THE PROJECT. IN AN EFFORT TO EXPEDITE THE | | | PERMITTING PROCESS, I CALLED THE ENGINEER OF RECORD- | | | MR. KARL LEDERER WHO ACKNOWLEDGED THAT THERE WERE NO | | | PLANS AT THE PRESENT TIME TO BE SUBMITTED. I ADVISED | | | HIM TO REVIEW THE APPLICABLE CODE SECTIONS FOR NAIL | | | SALONS IN THE FBC-2014 MECHANICAL CODE AND SUBMIT PLANS | | | ACCORDINGLY. PLEASE REFER TO TABLE 403.3 | | | FBC-MECHANICAL- FOR THE MINIMUM VENTILATION RATES | | | INCLUDING FOOTNOTES B & H AND SECTION 403.2.1 ITEM #3- | | | ALL OF WHICH ARE APPLICABLE TO NAIL SALONS. PLEASE | | | PROVIDE COMPLETE HVAC PLANS, EQUIPMENT SCHEDULES, | | | INSTALLATION DETAILS, AND CALCULATIONS FOR REVIEW. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|