Plan Review Notes
Plan Review Notes For Permit 15101064
Permit Number 15101064
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-11-04 11:20:21112 NORTH DIXIE HIGHWAY
 PERMIT #15101064
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 WHERE ARE ALL THE BUSINESS SUPPLIES TO BE LOCATED? PER
 SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF
 HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY
 (BUSINESS) OF THE BUILDING, SHALL BE SEPARATED FROM
 NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR
 BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS
 SHALL BE SELF CLOSING, POSITIVE LATCHING, AND
 FIRE-RATED FOR AT LEAST 45-MINUTES.
  
 PROVIDE AN OCCUPANT LOAD BREAKDOWN FOR EACH ROOM.
  
 FOR OCCUPANT LOADS OF 50 OR MORE PERSONS, DOORS SHALL
 SWING IN THE DIRECTION OF EGRESS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE ELECTRICAL PLAN DOES NOT INCLUDE THE EMERGENCY
 LIGHTING SHOWN ON THE LIFE SAFETY PLAN.
  
 NO MECHANICAL VENTILATION PLAN PROVIDED.
  