| Plan Review Notes For Permit 15101064 |
| Permit Number |
15101064 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-04 11:20:21 | 112 NORTH DIXIE HIGHWAY | | | PERMIT #15101064 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | WHERE ARE ALL THE BUSINESS SUPPLIES TO BE LOCATED? PER | | | SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF | | | HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY | | | (BUSINESS) OF THE BUILDING, SHALL BE SEPARATED FROM | | | NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR | | | BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS | | | SHALL BE SELF CLOSING, POSITIVE LATCHING, AND | | | FIRE-RATED FOR AT LEAST 45-MINUTES. | | | | | | PROVIDE AN OCCUPANT LOAD BREAKDOWN FOR EACH ROOM. | | | | | | FOR OCCUPANT LOADS OF 50 OR MORE PERSONS, DOORS SHALL | | | SWING IN THE DIRECTION OF EGRESS. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | THE ELECTRICAL PLAN DOES NOT INCLUDE THE EMERGENCY | | | LIGHTING SHOWN ON THE LIFE SAFETY PLAN. | | | | | | NO MECHANICAL VENTILATION PLAN PROVIDED. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|