Plan Review Notes
Plan Review Notes For Permit 15101064
Permit Number 15101064
Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-25 10:53:361ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 PLEASE PROVIDE ON PANEL SCHEDULE AND FLOOR PLAN
 EXIT/EMERGENCY LIGHTS AHEAD OF LIGHTING CIRCUITS PER
 ARTICLE 700 NEC 2011
 PLEASE PROVIDE AUTOMATIC LIGHTING SHUTOFF PER FBC
 ENERGY CODE SECTION C405.
 (B) OTHER THAN DWELLING UNITS. ALL 125-VOLT,
 SINGLEPHASE,
 15- AND 20-AMPERE RECEPTACLES INSTALLED IN THE
 LOCATIONS
 SPECIFIED IN 210.8(B)(1) THROUGH (8) SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 (1) BATHROOMS
 (2) KITCHENS
 (3) ROOFTOPS
 (4) OUTDOORS
 (B) LOAD EVENLY PROPORTIONED AMONG BRANCH CIRCUITS.
 WHERE THE LOAD IS CALCULATED ON THE BASIS OF
 VOLT-AMPERES
 PER SQUARE METER OR PER SQUARE FOOT, THE WIRING SYSTEM
 UP TO
 AND INCLUDING THE BRANCH-CIRCUIT PANELBOARD(S) SHALL BE
 PROVIDED
 TO SERVE NOT LESS THAN THE CALCULATED LOAD. THIS LOAD
 SHALL BE EVENLY PROPORTIONED AMONG MULTIOUTLET BRANCH
 CIRCUITS
 WITHIN THE PANELBOARD(S). BRANCH-CIRCUIT OVERCURRENT
 DEVICES AND CIRCUITS SHALL BE REQUIRED TO BE INSTALLED
 ONLY TO
 SERVE THE CONNECTED LOAD.
 ARTICLE 210?BRANCH CIRCUITS 210.11
 2011
 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED WITHIN 450 MM (18 IN.) OF THE TOP OF
 A
 SHOW WINDOW FOR EACH 3.7 LINEAR M (12 LINEAR FT) OR
 MAJOR
 FRACTION THEREOF OF SHOW WINDOW AREA MEASURED
 HORIZONTALLY
 AT ITS MAXIMUM WIDTH.
 .
  
  
  