2015-12-28 10:53:012ND REVIEW 2014 MECHANICAL
 PERMIT #15101055
 12/28/15
  
 1) THE DIMENSIONS OF THE SPRAY BOOTH SHOWN ON THE FIRE
 SUPPRESSION PLAN DOES NOT MATCH THE DIMENSIONS SHOWN ON
 THE SPRAY BOOTH PLANS. PLEASE REVISE AND INCLUDE THE
 MAKE AND MODEL NUMBER OF THE BOOTH ON THE SUPPRESSION
 PLAN.
 2) THE FIRE SUPPRESSION PLAN HAS ILLEGIBLE PRINT EITHER
 TOO SMALL OR FAINT TO READ AND SCAN FOR PUBLIC RECORD.
 PROVIDE ENLARGED LEGIBLE PLANS IN ACCORDANCE WITH
 SECTION 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  