| 2015-12-30 19:22:49 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1. YOU SHALL DEFINE YOUR SCOPE OF WORK AND INCLUDE IT |
| | ON THE PLANS. I CAN?T DETERMINE IF THIS IS PREFAB UNIT |
| | WITH A SINGLE POINT OF CONNECTION TO A FIELD PROVIDED |
| | DISCONNECT, OR IF THIS IS A SITE BUILT UNIT IN WHICH |
| | CASE FURTHER DETAILS SHALL BE PROVIDED. |
| | 2. ACCORDING TO THE MANUFACTURERS SPEC SHEET, BOTH THE |
| | EXHAUST AND SUPPLY FANS ARE 3 PHASE AND THE SERVICE TO |
| | THE PREMISES ARE INDICATED ON THE RISER DIAGRAM IS |
| | SINGLE PHASE. |
| | 3. PROVIDE LITERATURE OR MANUFACTURERS SPEC SHEETS FOR |
| | THE MOTORS, OR PROVIDE SOMETHING INDICATING WHETHER THE |
| | VALUES EXPRESSED ON PAGE 3 ARE MOTOR FLC, OR OCP. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |