Plan Review Notes
Plan Review Notes For Permit 15101055
Permit Number 15101055
Review Stop E
Sequence Number 2
Notes
Date Text
2015-12-30 19:22:49THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. YOU SHALL DEFINE YOUR SCOPE OF WORK AND INCLUDE IT
 ON THE PLANS. I CAN?T DETERMINE IF THIS IS PREFAB UNIT
 WITH A SINGLE POINT OF CONNECTION TO A FIELD PROVIDED
 DISCONNECT, OR IF THIS IS A SITE BUILT UNIT IN WHICH
 CASE FURTHER DETAILS SHALL BE PROVIDED.
 2. ACCORDING TO THE MANUFACTURERS SPEC SHEET, BOTH THE
 EXHAUST AND SUPPLY FANS ARE 3 PHASE AND THE SERVICE TO
 THE PREMISES ARE INDICATED ON THE RISER DIAGRAM IS
 SINGLE PHASE.
 3. PROVIDE LITERATURE OR MANUFACTURERS SPEC SHEETS FOR
 THE MOTORS, OR PROVIDE SOMETHING INDICATING WHETHER THE
 VALUES EXPRESSED ON PAGE 3 ARE MOTOR FLC, OR OCP.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,