| Plan Review Notes For Permit 15101055 |
| Permit Number |
15101055 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-13 11:38:32 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15101055 | | | 11/13/15 | | | | | | 1) THERE IS A DISCREPANCY IN THE PLANS AND | | | SPECIFICATIONS FOR THE CHINOOK II PAINT SPRAY BOOTH: | | | TWO DIFFERENT MODEL NUMBERS ARE LISTED ON SHEET A- | | | (#42106X IN THE DRAWING, AND #99830X IN THE NOTES). SEE | | | PAGE 3 OF THE SUBMITTED BOOTH SPECS- MODEL #42106X AS | | | SPECIFIED ON THE PLANS DOES NOT COME WITH A HEATER, | | | HOWEVER AN 840,000 BTUH GAS FIRED BURNER IS LISTED IN | | | THE NOTES ON SHEET A AND ON SHEET M-1. PLEASE CLARIFY | | | WHICH BOOTH IS TO BE INSTALLED AND IF A GAS-FIRED | | | HEATER IS INCLUDED. IN ACCORDANCE WITH THE BOOTH SPECS, | | | EXPLOSION VENTING IS REQUIRED IF HEATING IS PROVIDED | | | (PAGES 3, 8, & 16), AND IN NOTE #14 ON SHEET | | | UNOBSTRUCTED EXPLOSION RELIEF IS REQUIRED. PLEASE | | | PROVIDE DETAILS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|