2015-11-13 12:10:041ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15101045
 11/13/15
  
 1) THERE IS A DISCREPANCY IN THE PLANS AND
 SPECIFICATIONS FOR THE CHINOOK II PAINT SPRAY BOOTH:
 TWO DIFFERENT MODEL NUMBERS ARE LISTED ON SHEET A-
 (#42106X IN THE DRAWING, AND #99830X IN THE NOTES). SEE
 PAGE 3 OF THE SUBMITTED BOOTH SPECS- MODEL #42106X AS
 SPECIFIED ON THE PLANS DOES NOT COME WITH A HEATER,
 HOWEVER AN 840,000 BTUH GAS FIRED BURNER IS LISTED IN
 THE NOTES ON SHEET A AND ON SHEET M-1. PLEASE CLARIFY
 WHICH BOOTH IS TO BE INSTALLED AND IF A GAS-FIRED
 HEATER IS INCLUDED. IN ACCORDANCE WITH THE BOOTH SPECS,
 EXPLOSION VENTING IS REQUIRED IF HEATING IS PROVIDED
 (PAGES 3, 8, & 16), AND IN NOTE #14 ON SHEET
 UNOBSTRUCTED EXPLOSION RELIEF IS REQUIRED. PLEASE
 PROVIDE DETAILS.
 2) PROVIDE DETAILS FOR THE COMPRESSED AIR SYSTEM:
 EQUIPMENT SCHEDULE FOR THE COMPRESSOR, LOCATION OF THE
 COMPRESSOR, TYPE AND DIAMETER OF COMPRESSED AIR PIPING,
 LAYOUT OF PIPING RUNS, AND PIPE HANGING AND SUPPORT
 DETAILS.
 3) PLEASE CLARIFY OR CORRECT: PAGE 18 OF THE SPECS
 INDICATES SINGLE WALL PANELS AT 16 MSG, HOWEVER
 STRUCTURAL PANELS ARE LISTED AT 16 GAUGE STEEL ON M-1.
 4) PROVIDE AN AIR VELOCITY CALCULATION FOR THE BOOTH IN
 COMPLIANCE WITH SECTION 502.7.3.3 FBC-14 MECHANICAL.
 5) SHEET M-1: THE LOCATION OF THE AIR INTAKE SHALL BE
 LOCATED NOT LESS THAN 10' HORIZONTALLY FROM THE EXHAUST
 OUTLET- REFER TO SECTION 401.4 FBC-14 MECHANICAL.
 6) M-1 & M2: PLEASE INDICATE THE CLEARANCE DISTANCE
 MEASUREMENTS FROM THE EXHAUST OUTLET TO THE PROPERTY
 LINES: SEE SECTION 501.3.1 ITEM #1- 30' CLEARANCE
 REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  