| 2015-11-13 12:10:04 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15101045 |
| | 11/13/15 |
| | |
| | 1) THERE IS A DISCREPANCY IN THE PLANS AND |
| | SPECIFICATIONS FOR THE CHINOOK II PAINT SPRAY BOOTH: |
| | TWO DIFFERENT MODEL NUMBERS ARE LISTED ON SHEET A- |
| | (#42106X IN THE DRAWING, AND #99830X IN THE NOTES). SEE |
| | PAGE 3 OF THE SUBMITTED BOOTH SPECS- MODEL #42106X AS |
| | SPECIFIED ON THE PLANS DOES NOT COME WITH A HEATER, |
| | HOWEVER AN 840,000 BTUH GAS FIRED BURNER IS LISTED IN |
| | THE NOTES ON SHEET A AND ON SHEET M-1. PLEASE CLARIFY |
| | WHICH BOOTH IS TO BE INSTALLED AND IF A GAS-FIRED |
| | HEATER IS INCLUDED. IN ACCORDANCE WITH THE BOOTH SPECS, |
| | EXPLOSION VENTING IS REQUIRED IF HEATING IS PROVIDED |
| | (PAGES 3, 8, & 16), AND IN NOTE #14 ON SHEET |
| | UNOBSTRUCTED EXPLOSION RELIEF IS REQUIRED. PLEASE |
| | PROVIDE DETAILS. |
| | 2) PROVIDE DETAILS FOR THE COMPRESSED AIR SYSTEM: |
| | EQUIPMENT SCHEDULE FOR THE COMPRESSOR, LOCATION OF THE |
| | COMPRESSOR, TYPE AND DIAMETER OF COMPRESSED AIR PIPING, |
| | LAYOUT OF PIPING RUNS, AND PIPE HANGING AND SUPPORT |
| | DETAILS. |
| | 3) PLEASE CLARIFY OR CORRECT: PAGE 18 OF THE SPECS |
| | INDICATES SINGLE WALL PANELS AT 16 MSG, HOWEVER |
| | STRUCTURAL PANELS ARE LISTED AT 16 GAUGE STEEL ON M-1. |
| | 4) PROVIDE AN AIR VELOCITY CALCULATION FOR THE BOOTH IN |
| | COMPLIANCE WITH SECTION 502.7.3.3 FBC-14 MECHANICAL. |
| | 5) SHEET M-1: THE LOCATION OF THE AIR INTAKE SHALL BE |
| | LOCATED NOT LESS THAN 10' HORIZONTALLY FROM THE EXHAUST |
| | OUTLET- REFER TO SECTION 401.4 FBC-14 MECHANICAL. |
| | 6) M-1 & M2: PLEASE INDICATE THE CLEARANCE DISTANCE |
| | MEASUREMENTS FROM THE EXHAUST OUTLET TO THE PROPERTY |
| | LINES: SEE SECTION 501.3.1 ITEM #1- 30' CLEARANCE |
| | REQUIRED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |