 . CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES
  
 (B) ELECTRICAL EQUIPMENT INSTALLED ABOVE CLASS I
 LOCATIONS.
 (1) FIXED ELECTRICAL EQUIPMENT. ELECTRICAL EQUIPMENT IN
 A
 FIXED POSITION SHALL BE LOCATED ABOVE THE LEVEL OF ANY
 DEFINED
 CLASS I LOCATION OR SHALL BE IDENTIFIED FOR THE
 LOCATION.
 (A) ARCING EQUIPMENT. EQUIPMENT THAT IS LESS THAN 3.7 M
 (12 FT) ABOVE THE FLOOR LEVEL AND THAT MAY PRODUCE
 ARCS, SPARKS,
 OR PARTICLES OF HOT METAL, SUCH AS CUTOUTS, SWITCHES,
 CHARGING
 PANELS, GENERATORS, MOTORS, OR OTHER EQUIPMENT
 (EXCLUDING RECEPTACLES,
 LAMPS, AND LAMPHOLDERS) HAVING MAKE-AND-BREAK OR
 SLIDING CONTACTS, SHALL BE OF THE TOTALLY ENCLOSED TYPE
 OR CONSTRUCTED
 SO AS TO PREVENT THE ESCAPE OF SPARKS OR HOT METAL
 PARTICLES.
 (B) FIXED LIGHTING. LAMPS AND LAMPHOLDERS FOR FIXED
 LIGHTING THAT IS LOCATED OVER LANES THROUGH WHICH
 VEHICLES
 ARE COMMONLY DRIVEN OR THAT MAY OTHERWISE BE EXPOSED TO
 PHYSICAL DAMAGE SHALL BE LOCATED NOT LESS THAN 3.7 M
 (12 FT)
 ABOVE FLOOR LEVEL, UNLESS OF THE TOTALLY ENCLOSED TYPE
 OR
 CONSTRUCTED SO AS TO PREVENT ESCAPE OF SPARKS OR HOT
 METAL
 PARTICLES.
  
 SHOW ELECTRICAL EQUIPMENT ON SITE PLAN TO SEE IF
 LOCATIONS COMPLY WITH NEC HAZARDOUS REQUIREMENTS.
  
 NO GROUNDING DETAIL IN RISER DIAGRAM PER ARTICLE 250.66
 NEC
  
 PLEASE PROVIDE WIRE GUTTER SIZE MAKE SURE IT COMPLIES
 WITH NEC 366.22
  
 PLEASE PROVIDE AIC CACULATION FOR SERVICE FUSES
 DISCONNECT.
  
  