| 2015-11-30 09:21:31 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6700 |
| | [email protected] |
| | ALTERNATE CONTACT |
| | PHIL PETTY |
| | 561-805-6742 |
| | [email protected] |
| | |
| | |
| | |
| | . CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES |
| | |
| | (B) ELECTRICAL EQUIPMENT INSTALLED ABOVE CLASS I |
| | LOCATIONS. |
| | (1) FIXED ELECTRICAL EQUIPMENT. ELECTRICAL EQUIPMENT IN |
| | A |
| | FIXED POSITION SHALL BE LOCATED ABOVE THE LEVEL OF ANY |
| | DEFINED |
| | CLASS I LOCATION OR SHALL BE IDENTIFIED FOR THE |
| | LOCATION. |
| | (A) ARCING EQUIPMENT. EQUIPMENT THAT IS LESS THAN 3.7 M |
| | (12 FT) ABOVE THE FLOOR LEVEL AND THAT MAY PRODUCE |
| | ARCS, SPARKS, |
| | OR PARTICLES OF HOT METAL, SUCH AS CUTOUTS, SWITCHES, |
| | CHARGING |
| | PANELS, GENERATORS, MOTORS, OR OTHER EQUIPMENT |
| | (EXCLUDING RECEPTACLES, |
| | LAMPS, AND LAMPHOLDERS) HAVING MAKE-AND-BREAK OR |
| | SLIDING CONTACTS, SHALL BE OF THE TOTALLY ENCLOSED TYPE |
| | OR CONSTRUCTED |
| | SO AS TO PREVENT THE ESCAPE OF SPARKS OR HOT METAL |
| | PARTICLES. |
| | (B) FIXED LIGHTING. LAMPS AND LAMPHOLDERS FOR FIXED |
| | LIGHTING THAT IS LOCATED OVER LANES THROUGH WHICH |
| | VEHICLES |
| | ARE COMMONLY DRIVEN OR THAT MAY OTHERWISE BE EXPOSED TO |
| | PHYSICAL DAMAGE SHALL BE LOCATED NOT LESS THAN 3.7 M |
| | (12 FT) |
| | ABOVE FLOOR LEVEL, UNLESS OF THE TOTALLY ENCLOSED TYPE |
| | OR |
| | CONSTRUCTED SO AS TO PREVENT ESCAPE OF SPARKS OR HOT |
| | METAL |
| | PARTICLES. |
| | |
| | SHOW ELECTRICAL EQUIPMENT ON SITE PLAN TO SEE IF |
| | LOCATIONS COMPLY WITH NEC HAZARDOUS REQUIREMENTS. |
| | |
| | NO GROUNDING DETAIL IN RISER DIAGRAM PER ARTICLE 250.66 |
| | NEC |
| | |
| | PLEASE PROVIDE WIRE GUTTER SIZE MAKE SURE IT COMPLIES |
| | WITH NEC 366.22 |
| | |
| | PLEASE PROVIDE AIC CACULATION FOR SERVICE FUSES |
| | DISCONNECT. |
| | |
| | |