Plan Review Notes
Plan Review Notes For Permit 15101027
Permit Number 15101027
Review Stop E
Sequence Number 2
Notes
Date Text
2016-01-27 15:48:08YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS. THESE PLANS HAVE BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE) AND THE FBC, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS IN EFFECT AT THE TIME OF SUBMITTAL.
  
 PER THE NOTES ON THE FIRST ELECTRICAL REVIEW, YOU WERE
 INSTRUCTED TO SUBMIT A NARRATIVE INDICATING THE ACTION
 TAKEN TO ADDRESS EACH COMMENT NOTED. BELOW IS THE
 RESULT OF THE FAILED SECOND REVIEW.
  
 COMMENT 1. NEC 210.62: AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A SHOW
 WINDOW FOR EACH 12 LINEAR FT. OR MAJOR PORTION THEREOF
 OF SHOW WINDOW AREA MEASURED HORIZONTALLY.
 REVIEW RESULT: THERE IS NO INDICATION ON THE PLANS THAT
 THIS HAS BEEN ADDRESSED. I DO NOT SEE SHOW WINDOW
 OUTLETS ON THE PLANS.
  
 COMMENT 2. NEC 215.5: A DIAGRAM SHALL BE PROVIDED
 SHOWING FEEDER DETAILS. THIS DIAGRAM SHALL INCLUDE LOAD
 CALCULATIONS, CONDUCTOR SIZING AND TYPE OF INSULATION
 USED.
 REVIEW RESULT: YOU WERE ASKED FOR A RISER DIAGRAM WITH
 LOAD CALCS AND CONDUCTOR SIZING AND RATING. ON THE
 SUBMITTED DIAGRAM YOU FAIL TO INCLUDE THE SOURCE OF
 PANEL H. YOU SHALL INCLUDE THE CONDUCTOR SIZING FOR THE
 PANELS. FURTHERMORE, AS A RESULT OF THE NEW RISER YOU
 INCLUDED PANEL L1 WITH A CONNECTED LOAD OF 81 AMP (29.2
 KVA*1000/360=81) AND AN OCPD OF 60 AMP. IS THIS PANEL
 WIRED FOR THE 60 AMP PER THE OCPD, 80 AMPS PER THE
 CONNECTED LOAD OR THE 150 AMP FOR THE BUS?
  
 COMMENT 3. NEC 600.5: EACH COMMERCIAL ESTABLISHMENT
 ACCESSIBLE TO PEDESTRIANS SHALL HAVE AT LEAST ONE
 OUTLET IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE FOR
 SIGN OR OUTLINE LIGHTING SYSTEM.
 REVIEW RESULT: THE CODE SECTION CLEARLY STATES A SIGN
 OUTLET IS REQUIRED AT EACH PEDESTRIAN ENTRY. YOU HAVE
 PROVIDED THE REQUIRED OUTLET AT THE MAIN ENTRY ONLY.
 COMMENT 4. FBC?E C402.4.8: RECESSED LIGHTING INSTALLED
 IN THE BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND
 SEALED TO LIMIT THE TRANSFER OF AIR BETWEEN CONDITIONED
 AND UNCONDITIONED SPACE.
 REVIEW RESULT: NOW THAT A FIXTURE SCHEDULE HAS BEEN
 SUBMITTED, IT IS INDICATED THAT RECESSED LIGHTING WILL
 NOT BE USED.
  
 COMMENT 5. FBC?EC405.5: SHOW COMPLIANCE WITH INTERIOR
 LIGHTING POWER REQUIREMENTS AS INDICATED BY SECTIONS
 C405.5.1 & C405.5.2.
 REVIEW RESULT: LIGHT DENSITY CALCULATIONS SHALL BE
 CORRECTED AND THE LIGHTING DESIGNED TO COMPLY. LIGHTING
 POWER ALLOWANCES BUILDING AREA METHOD, WHICH IS WHAT
 YOU APPEAR TO HAVE USED, INDICATES THAT THE ALLOWABLE
 W/FT2 FOR AN OFFICE IS 0.9. THE OCCUPANCY ANALYSIS
 REFLECTS THE AREA TO BE 5843 FT2. THEREFORE THE
 ALLOWABLE LIGHT DENSITY IS 5258.7 WATTS. THE 33
 FLUORESCENTS AT 28 W/EA. ALONG WITH THE 77 DOWN LIGHTS
 AT 19 W/EA. PUTS YOU BEYOND THE ALLOWABLE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  