Plan Review Notes
Plan Review Notes For Permit 15101027
Permit Number 15101027
Review Stop P
Sequence Number 1
Notes
Date Text
2015-11-23 14:03:2311/23/15 ON MALBARRAN'S DESK. CP
2015-11-16 12:52:301) FOR A BUSINESS OCCUPANCY WITH AN OCCUPANT LOAD OF 59
 PERSONS A TOTAL OF 2 WATER CLOSETS ARE REQUIRED FOR THE
 MALES AND 2 WATER CLOSETS ARE REQUIRED FOR THE FEMALES
 PER TABLE 403.1 OF THE 2014 FBC-PLUMBING.
 2) A DRINKING FOUNTAIN IS REQUIRED PER 2014
 FBC-PLUMBING TABLE 403.1. A MINIMUM OF 2 DRINKING
 FOUNTAINS ARE REQUIRED PER TABLE 403.1 FOOTNOTE (E) AND
 THE 2014 FBC-ACCESSIBILITY SEC.211.2.
 3) SEE BUILDING PLAN REVIEW COMMENT REGARDING THE
 OCCUPANCY TYPE OF THIS SPACE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  