Plan Review Notes
Plan Review Notes For Permit 15101027
Permit Number 15101027
Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-25 11:10:18THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. NEC 210.62: AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR
 EACH 12 LINEAR FT. OR MAJOR PORTION THEREOF OF SHOW
 WINDOW AREA MEASURED HORIZONTALLY.
 2. NEC 215.5: A DIAGRAM SHALL BE PROVIDED SHOWING
 FEEDER DETAILS. THIS DIAGRAM SHALL INCLUDE LOAD
 CALCULATIONS, CONDUCTOR SIZING AND TYPE OF INSULATION
 USED.
 3. NEC 600.5: EACH COMMERCIAL ESTABLISHMENT ACCESSIBLE
 TO PEDESTRIANS SHALL HAVE AT LEAST ONE OUTLET IN AN
 ACCESSIBLE LOCATION AT EACH ENTRANCE FOR SIGN OR
 OUTLINE LIGHTING SYSTEM.
 4. FBC-E C402.4.8: RECESSED LIGHTING INSTALLED IN THE
 BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND SEALED
 TO LIMIT THE TRANSFER OF AIR BETWEEN CONDITIONED AND
 UNCONDITIONED SPACE.
 5. FBC-EC405.5: SHOW COMPLIANCE WITH INTERIOR LIGHTING
 POWER REQUIREMENTS AS INDICATED BY SECTIONS C405.5.1 &
 C405.5.2
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  