| 2015-11-25 11:10:18 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. NEC 210.62: AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| | INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR |
| | EACH 12 LINEAR FT. OR MAJOR PORTION THEREOF OF SHOW |
| | WINDOW AREA MEASURED HORIZONTALLY. |
| | 2. NEC 215.5: A DIAGRAM SHALL BE PROVIDED SHOWING |
| | FEEDER DETAILS. THIS DIAGRAM SHALL INCLUDE LOAD |
| | CALCULATIONS, CONDUCTOR SIZING AND TYPE OF INSULATION |
| | USED. |
| | 3. NEC 600.5: EACH COMMERCIAL ESTABLISHMENT ACCESSIBLE |
| | TO PEDESTRIANS SHALL HAVE AT LEAST ONE OUTLET IN AN |
| | ACCESSIBLE LOCATION AT EACH ENTRANCE FOR SIGN OR |
| | OUTLINE LIGHTING SYSTEM. |
| | 4. FBC-E C402.4.8: RECESSED LIGHTING INSTALLED IN THE |
| | BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND SEALED |
| | TO LIMIT THE TRANSFER OF AIR BETWEEN CONDITIONED AND |
| | UNCONDITIONED SPACE. |
| | 5. FBC-EC405.5: SHOW COMPLIANCE WITH INTERIOR LIGHTING |
| | POWER REQUIREMENTS AS INDICATED BY SECTIONS C405.5.1 & |
| | C405.5.2 |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |