| Plan Review Notes For Permit 15101018 |
| Permit Number |
15101018 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-12 05:40:20 | 1) SUBMIT SIZING CALCULATIONS FOR THE HYDROMECHANICAL | | | GREASE INTERCEPTOR UNIT. THE INTERCEPTOR SHALL BE SIZED | | | IN ACCORDANCE WITH STANDARD PDI-G 101 (PLUMBING AND | | | DRAINAGE INSTITUTE) AS REFERENCED IN 2014 FBC | | | -PLUMBING, SEC.1003.3.4. | | | 2) SUBMIT MABNUFACTURER'S SPECIFICATIONS/INSTALLATION | | | MANUAL FOR THE GREASE INTERCEPTOR. WPB AMEND. TO FBC | | | SEC.107.3.5.1.3. | | | 3) THE WATER SUPPLY TO THE ICE MACHINE SHALL BE | | | PROTECTED AGAINST BACKFLOW IN ACCORDANCE WITH 2014 FBC | | | SEC.608.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|