Plan Review Notes
Plan Review Notes For Permit 15101018
Permit Number 15101018
Review Stop P
Sequence Number 1
Notes
Date Text
2015-11-12 05:40:201) SUBMIT SIZING CALCULATIONS FOR THE HYDROMECHANICAL
 GREASE INTERCEPTOR UNIT. THE INTERCEPTOR SHALL BE SIZED
 IN ACCORDANCE WITH STANDARD PDI-G 101 (PLUMBING AND
 DRAINAGE INSTITUTE) AS REFERENCED IN 2014 FBC
 -PLUMBING, SEC.1003.3.4.
 2) SUBMIT MABNUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE GREASE INTERCEPTOR. WPB AMEND. TO FBC
 SEC.107.3.5.1.3.
 3) THE WATER SUPPLY TO THE ICE MACHINE SHALL BE
 PROTECTED AGAINST BACKFLOW IN ACCORDANCE WITH 2014 FBC
 SEC.608.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR