2015-11-09 07:38:241ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15101018
 11/9/15
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 ON THE PLAN INCLUDING A NEW DUCT LAYOUT PLAN AND AIR
 DISTRIBUTION SCHEDULE.
 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING AND
 PROVIDE A VENTILATION CALULATION ON THE PLAN IN
 COMPLIANCE WITH TABLE 403.3 FBC-14 MECHANICAL. SHOW THE
 REQUIRED AMOUNT OF CFM'S OF OUTDOOR AIR, AND THE AMOUNT
 OF CFM'S BEING PROVIDED BY THE EXISTING SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER