Plan Review Notes
Plan Review Notes For Permit 15101018
Permit Number 15101018
Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-25 13:40:501ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 NEC 210.11(B) OTHER THAN DWELLING UNITS. ALL 125-VOLT,
 SINGLEPHASE,
 15- AND 20-AMPERE RECEPTACLES INSTALLED IN THE
 LOCATIONS
 SPECIFIED IN 210.8(B)(1) THROUGH (8) SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 (1) BATHROOMS
 (2) KITCHENS X
 (3) ROOFTOPS
 (4) OUTDOORS
  
  
 PLEASE PROVIDE LIGHTING PLAN WITH ENERGY CODE CONTROLS
 FBC ENERGY C 405
 PLEASE MAKE SURE PANEL SCHEDULE REFLECTS POWER PLAN (
 CIRCUIT # A 21-23 FOR NEW W/H SHOWN AS SPARE )
  