| Plan Review Notes For Permit 15101018 |
| Permit Number |
15101018 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-25 13:40:50 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | PHIL PETTY | | | 561-805-6742 | | | [email protected] | | | | | | | | | NEC 210.11(B) OTHER THAN DWELLING UNITS. ALL 125-VOLT, | | | SINGLEPHASE, | | | 15- AND 20-AMPERE RECEPTACLES INSTALLED IN THE | | | LOCATIONS | | | SPECIFIED IN 210.8(B)(1) THROUGH (8) SHALL HAVE | | | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR | | | PERSONNEL. | | | (1) BATHROOMS | | | (2) KITCHENS X | | | (3) ROOFTOPS | | | (4) OUTDOORS | | | | | | | | | PLEASE PROVIDE LIGHTING PLAN WITH ENERGY CODE CONTROLS | | | FBC ENERGY C 405 | | | PLEASE MAKE SURE PANEL SCHEDULE REFLECTS POWER PLAN ( | | | CIRCUIT # A 21-23 FOR NEW W/H SHOWN AS SPARE ) | | | |
|