| 2015-11-02 09:17:26 | 1) SUBMIT A GAS PIPING RISER FOR REVIEW. SHOW THE TYPE | | | OF PIPE MATERIAL, THE TOTAL BTU LOAD ON THE SYSTEM, THE | | | DISTANCE OF THE MOST REMOTE OUTLET FROM THE SOURCE TO | | | THE MOST REMOTE OUTLET AND THE PIPE SIZE. INDICATE THE | | | SPECIFIC SIZING TABLE FROM THE CODE THAT THE SYSTEM IS | | | BASED ON. WPB AMEND. TO FBC SEC. 107. | | | 2) INDICATE THE LOCATION OF THE GAS PIPING ON THE PLAN. | | | IS THIS NEW GAS PIPING OR IS THE DRYER CONNECTING TO AN | | | EXISTING OUTLET? IS THE DRYER BEING RELOCATED OR IS | | | THIS AN ADDITIONAL GAS LOAD ON AN EXISTING SYSTEM ? | | | SHOW WHAT IS NEW AND EXISTING. CLARIFY. | | | 3) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR THE GAS | | | APPLIANCES.APPLIANCES SHALL BE LISTED AND LABELED PER | | | THE 2014 FBC SER. G2404.3. | | | 4) SUBMIT DETAILS / CALCULATIONS FOR COMBUSTION AIR FOR | | | THE GAS DRYER PER THE 2014 FBC-RESIDENTIAL SEC. G2407. | | | 5) SUBMIT DETAILS FOR THE GAS DRYER EXHAUST.CLOTHES | | | DRYER EXHAUST SHALL CCOMPLY WITH THE 2014 FBC- | | | RESIDENTIAL SEC. G2439. UNITS EXHAUSTING MORE THAN 200 | | | CFM SHALL BE PROVIDED WITH MAKEUP AIR PER SEC. | | | G2439.4.SUBMIT THE INSTALLATION MANUAL FOR REVIEW. | | | 6) INDICATE THE TYPE OF GAS (NATURAL OR LP). | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|