| 2015-11-09 16:50:52 | |
| | 1ST REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS |
| | |
| | 1.PLEASE SUBMIT SIGNED AND SEALED CIVIL DRAWINGS |
| | SHOWING SANITARY SEWER ,WATER SERVICE,AND STORM. |
| | PER WPB AMEND.TO FBC SEC 107.2.1 |
| | 2. SHEET P-3 IT APPEARS THAT HALF THE ROOF IS BEING |
| | DRAINED BY A ROOF DRAIN AND HALF BY SCUPPERS PLEASE |
| | CLARIFY. |
| | 3. PROVIDE SIZING CALCULATIONS FOR ALL GUTTERS |
| | ,SCUPPERS AND ROOF DRAINS. |
| | PER WPB AMEND.TO FBC SEC 107.2.1.3 |
| | 4.ALL DRAINS IN FOOD AND DRINK PREP AND SERVICE AREAS |
| | SHALL BE ON THE GREASE SYSTEM. |
| | PER FBC P SEC 1003.3.1 |
| | 5. PLEASE PROVIDE MANUFACTURE SPEC SHEETS AND |
| | INSTILLATION GUIDES FOR WATER SOFTENER, AND FILER |
| | SYSTEMS, PRESSURE WASHER, SANITIZER , |
| | PER.WPB AMEND.TO FBC SEC 107.2.1 |
| | 6. SHEET P1 SHOW TRAP PRIMERS FOR ALL FLOOR DRAINS. |
| | PER.WPB AMEND.TO FBC SEC 107.2.1 |
| | |
| | 1111.4 MINIMUM NUMBER OF ROOF DRAINS. |
| | NOT LESS THAN TWO ROOF DRAINS SHALL BE INSTALLED IN |
| | ROOF AREAS 10,000 SQUARE FEET (929 M2) OR LESS AND NOT |
| | LESS THAN FOUR ROOF DRAINS SHALL BE INSTALLED IN ROOFS |
| | OVER 10,000 SQUARE FEET (929 M 2 ) IN AREA. |
| | |
| | A COMPLETE COMPREHENSIVE REVIEW CAN NOT BE COMPLETED AT |
| | THIS TIME DO TO LACK OF INFORMATION . THERE MAYBE |
| | ADDITIONAL COMMENTS ON SECOND REVIEW WHEN INFO IS |
| | PROVIDED. |