Plan Review Notes
Plan Review Notes For Permit 15100991
Permit Number 15100991
Review Stop P
Sequence Number 3
Notes
Date Text
2016-05-02 10:52:51PLUMBING PROVISO
 1. PROVIDE TWO SIGNED AND SEALED COPIES OF GREASE
 INTERCEPTOR CALCULATIONS REFERENCING PDI G101 NOT FBC.
 SHALL PROVIDE BEFORE ROUGH INSPECTION. PER WPB AMEND.
 TO FBC SEC 107.2.1
 2. PROVIDE TWO SETS OF APPROVED AND SIGNED AND SEALED
 CIVIL PLANS BEFORE FIRST ROUGH INSPECTION.
 PER WPB AMEND. TO FBC SEC 107.2.1
  
 3. HAND SINKS SHALL NOT BE CONNECTED TO GREASE DRAIN.
 FBC PL 1003.3.1
  
  