| 2016-05-14 15:00:35 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100991 WAWA CONVENIENCE STORE |
| | ADD: 1520 BELVEDERE RD. |
| | CONT: TBD( TO BE DETERMINED) |
| | TEL: 407-661-9100 X2462 |
| | E-MAIL: [email protected] |
| | |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: SAT. MAY 15/2016 |
| | ACTION: DENIED |
| | |
| | 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM |
| | BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT |
| | APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR |
| | WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER |
| | 7/1/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $500,000. PER CITY OF WEST |
| | PALM BEACH ORDINANCE NO. 4504-14, AND CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC |
| | PLACES, SECTION 78-123(A) AND SECTION 78-126(A), THE |
| | ART ASSESSMENT IS 1% OF THE TOTAL PROJECT CONSTRUCTION |
| | COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS |
| | |
| | 2) COMPLIED. SITE PLAN SUBMITTED. |
| | |
| | 3) SEMI-COMPLIED. SUBMITTED SOILS REPORT FOR A |
| | QUESTIONABLE SOIL ZONE . |
| | SEE COMMENTS FROM 2ND REVIEW ON VARYING DEPTHS OF |
| | SUSPECTED BURIED DEBRIS. |
| | |
| | 3A) 3RD. THE STRUCTURAL ENGINEER OF RECORD PLEASE |
| | RESPOND WHAT STEPS ARE GOING TO BE UNDERTAKEN TO MAKE |
| | THIS SITE A FOR A STABLE FOUNDATION AND BUILDABLE FOR |
| | THIS TYPE OF STRUCTURE. |
| | THE RESPONSE LETTER COMES FROM MOLLI LINDSEY NOT THE |
| | STRUCTURAL ENGINEER OF RECORD. PLEASE ALLOW THE |
| | STRUCTURAL ENGINEER TO WRITE THEIR OWN RESPONSE. |
| | |
| | 3B) THE PERMITTING COORDINATOR INDICATES THIS IS NOT IN |
| | THE SCOPE OF THEIR WORK. PLEASE NOTE THE AMOUNT OF |
| | DEBRIS TO BE REMOVED AND THE FILL TO BE BROUGHT BACK IN |
| | WILL ALSO BE REVIEWED BY THE ENGINEER OF RECORD SINCE |
| | THERE IS A CLOSENESS OF THE TANKS TO THE CANOPY |
| | FOUNDATION, IF SHEET PILING ARE GOING TO BE USED AS |
| | WELL AS IN WHAT ORDER OF WORK WILL THE UNDERGROUND |
| | TANKS BE INSTALLED 1ST. |
| | |
| | |
| | COMMENT FROM 1ST REVIEW. 2014 FLORIDA BUILDING CODE W |
| | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION. 107.3.5.1.1 MINIMUM |
| | PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. (8.) |
| | STRUCTURAL REQUIREMENTS SHALL INCLUDE: SOIL |
| | CONDITIONS/ANALYSIS |
| | 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 4) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: 7.) |
| | FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION STEEL STRUCTURE WHERE EITHER |
| | STEEL IS WELDED OR BOLTED TOGETHER. |
| | |
| | 4A) 3RD REQUEST. RESIDENT INSPECTOR FORMS MUST BE |
| | SIGNED BY ALL PARTIES NOTARIZED AND RETURNED TO THE |
| | BUILDING DEPARTMENT. FORMS WERE SENT TO: |
| | 1) [email protected] MON. NOV. 23/2015 @ 08:14 AM. |
| | 2) MOLLIL@C-P,COM SUN. FEB. 21/ 2016 @ 07:54 AM. |
| | |
| | 4B) 3RD REQUEST. FOR THE RESIDENT INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| | |
| | 4C) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 4D) 3RD REQUEST. NOTE FOR PAPER PLANS 3 SETS OF |
| | DOCUMENTS ARE REQUIRED. NOTE ONLY 2 SETS OF SOILS |
| | REPORTS, PRODUCT APPROVALS, LENNOX ROOF TOP CLIP |
| | CALCULATIONS AND ENERGY CALCULATIONS SUBMITTED. |
| | |
| | 4E) INFORMATIONAL. PLEASE CALL THE CITY OF WEST PALM |
| | BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS. |
| | |
| | 5) COMPLIED. SUBMITTAL: ROOF CURB CLIP CALCULATIONS BY |
| | THOMAS RETSECK P. E. FL. # 46462 |
| | |
| | 6) COMPLIED. THE FRONT COVER SHEET LIST 6 PRODUCT |
| | APPROVALS SUBMITTED: |
| | 1) ATAS DUTCH METAL ROOFING FL 3556R-5 |
| | 2) KAWNEER WINDOW NOA 14-02130.18 |
| | 3) KAWNEER DOOR NOA 14-0602.02 |
| | 4) JAMES HARDI NOA 15-0122.03 |
| | 5) BORAL STONE FL 1504.7 / 100378.05 R-3 |
| | 6) BASF PERMALATH 1000 GLASS FIBER LATH ERS-2429 |
| | |
| | 7A) BUILDING PROVISO: DEFERRED SUBMITTALS. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | |
| | |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. METAL EXTERIOR DOORS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES,R-40 ROOF TOP |
| | INSULATION, ASSEMBLIES FOR FLAT ROOF, ROOF TOP |
| | EXHAUST FANS |
| | (E) SHUTTERS- BAHAMA SHUTTERS |
| | (G) PRE-ENGINEERED ROOF TOP A/C STANDS |
| | (H) ROOF TOP LADDER( SHOP DRAWINGS) |
| | |
| | 7B)PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 8-9) COMPLIED |
| | |
| | 10) NEW COMMENT BASED ON THE RESPONSE. PLEASE PROVIDE A |
| | COPY OF THE TEST REPORT WALK IN FREEZER PANELS |
| | CLASSIFIED IN ACCORDANCE WITH UL 1715 TO DOCUMENT NO |
| | FIRE SPRINKLERS REQUIRED. THANK YOU. |
| | COMMENT FROM 2ND REVIEW. THE FLOOR PLAN SHEET A1 SHOWS |
| | THIS A BUILDING TYPE VB NON-SPRINKLERED BUILDING. SHOWS |
| | VARIOUS WALK IN COOLERS AND FREEZERS. PLEASE NOTE THEY |
| | WILL REQUIRE A SEPARATE PERMIT. THE ISSUE IS THIS IS A |
| | NON-SPRINKLERED BUILDING. PLEASE REVIEW THE 2014 FBC-B |
| | 2603.4.1.2 (4)COOLERS AND FREEZER WALLS. |
| | 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 903.3.1.1. WHERE THE COOLER OR |
| | FREEZER IS WITHIN A BUILDING, BOTH THE COOLER OR |
| | FREEZER AND THAT PART OF THE BUILDING IN WHICH IT IS |
| | LOCATED SHALL BE SPRINKLERED. |
| | |
| | THE EXCEPTION TO THIS IS FOUND UNDER SECTION 2603.4.1.3 |
| | WALK-IN COOLERS. IN NON-SPRINKLERED BUILDINGS, FOAM |
| | PLASTIC HAVING A THICKNESS THAT DOES NOT EXCEED 4 |
| | INCHES (102 MM) AND A MAXIMUM FLAME SPREAD INDEX OF 75 |
| | IS PERMITTED IN WALK-IN COOLERS OR FREEZER UNITS WHERE |
| | THE AGGREGATE FLOOR AREA DOES NOT EXCEED 400 SQUARE |
| | FEET (37 M2) AND THE FOAM PLASTIC IS COVERED BY A METAL |
| | FACING NOT LESS THAN 0.032-INCH-THICK (0.81 MM) |
| | ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A MINIMUM |
| | BASE METAL THICKNESS OF 0.016 INCH (0.41 MM). A |
| | THICKNESS OF UP TO 10 INCHES (254 MM) IS PERMITTED |
| | WHERE PROTECTED BY A THERMAL BARRIER. |
| | |
| | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | |