2016-05-14 15:00:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100991 WAWA CONVENIENCE STORE
 ADD: 1520 BELVEDERE RD.
 CONT: TBD( TO BE DETERMINED)
 TEL: 407-661-9100 X2462
 E-MAIL: [email protected]
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SAT. MAY 15/2016
 ACTION: DENIED
  
 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 7/1/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $500,000. PER CITY OF WEST
 PALM BEACH ORDINANCE NO. 4504-14, AND CITY OF WEST PALM
 BEACH CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC
 PLACES, SECTION 78-123(A) AND SECTION 78-126(A), THE
 ART ASSESSMENT IS 1% OF THE TOTAL PROJECT CONSTRUCTION
 COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS
  
 2) COMPLIED. SITE PLAN SUBMITTED.
  
 3) SEMI-COMPLIED. SUBMITTED SOILS REPORT FOR A
 QUESTIONABLE SOIL ZONE .
 SEE COMMENTS FROM 2ND REVIEW ON VARYING DEPTHS OF
 SUSPECTED BURIED DEBRIS.
  
 3A) 3RD. THE STRUCTURAL ENGINEER OF RECORD PLEASE
 RESPOND WHAT STEPS ARE GOING TO BE UNDERTAKEN TO MAKE
 THIS SITE A FOR A STABLE FOUNDATION AND BUILDABLE FOR
 THIS TYPE OF STRUCTURE.
 THE RESPONSE LETTER COMES FROM MOLLI LINDSEY NOT THE
 STRUCTURAL ENGINEER OF RECORD. PLEASE ALLOW THE
 STRUCTURAL ENGINEER TO WRITE THEIR OWN RESPONSE.
  
 3B) THE PERMITTING COORDINATOR INDICATES THIS IS NOT IN
 THE SCOPE OF THEIR WORK. PLEASE NOTE THE AMOUNT OF
 DEBRIS TO BE REMOVED AND THE FILL TO BE BROUGHT BACK IN
 WILL ALSO BE REVIEWED BY THE ENGINEER OF RECORD SINCE
 THERE IS A CLOSENESS OF THE TANKS TO THE CANOPY
 FOUNDATION, IF SHEET PILING ARE GOING TO BE USED AS
 WELL AS IN WHAT ORDER OF WORK WILL THE UNDERGROUND
 TANKS BE INSTALLED 1ST.
  
  
 COMMENT FROM 1ST REVIEW. 2014 FLORIDA BUILDING CODE W
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION. 107.3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. (8.)
 STRUCTURAL REQUIREMENTS SHALL INCLUDE: SOIL
 CONDITIONS/ANALYSIS
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 4) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: 7.)
 FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION STEEL STRUCTURE WHERE EITHER
 STEEL IS WELDED OR BOLTED TOGETHER.
  
 4A) 3RD REQUEST. RESIDENT INSPECTOR FORMS MUST BE
 SIGNED BY ALL PARTIES NOTARIZED AND RETURNED TO THE
 BUILDING DEPARTMENT. FORMS WERE SENT TO:
 1) [email protected] MON. NOV. 23/2015 @ 08:14 AM.
 2) MOLLIL@C-P,COM SUN. FEB. 21/ 2016 @ 07:54 AM.
  
 4B) 3RD REQUEST. FOR THE RESIDENT INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 4C) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4D) 3RD REQUEST. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. NOTE ONLY 2 SETS OF SOILS
 REPORTS, PRODUCT APPROVALS, LENNOX ROOF TOP CLIP
 CALCULATIONS AND ENERGY CALCULATIONS SUBMITTED.
  
 4E) INFORMATIONAL. PLEASE CALL THE CITY OF WEST PALM
 BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 5) COMPLIED. SUBMITTAL: ROOF CURB CLIP CALCULATIONS BY
 THOMAS RETSECK P. E. FL. # 46462
  
 6) COMPLIED. THE FRONT COVER SHEET LIST 6 PRODUCT
 APPROVALS SUBMITTED:
 1) ATAS DUTCH METAL ROOFING FL 3556R-5
 2) KAWNEER WINDOW NOA 14-02130.18
 3) KAWNEER DOOR NOA 14-0602.02
 4) JAMES HARDI NOA 15-0122.03
 5) BORAL STONE FL 1504.7 / 100378.05 R-3
 6) BASF PERMALATH 1000 GLASS FIBER LATH ERS-2429
  
 7A) BUILDING PROVISO: DEFERRED SUBMITTALS. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. METAL EXTERIOR DOORS
 (D) ROOFING PRODUCTS AND ASSEMBLIES,R-40 ROOF TOP
 INSULATION, ASSEMBLIES FOR FLAT ROOF, ROOF TOP
 EXHAUST FANS
 (E) SHUTTERS- BAHAMA SHUTTERS
 (G) PRE-ENGINEERED ROOF TOP A/C STANDS
 (H) ROOF TOP LADDER( SHOP DRAWINGS)
  
 7B)PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 8-9) COMPLIED
  
 10) NEW COMMENT BASED ON THE RESPONSE. PLEASE PROVIDE A
 COPY OF THE TEST REPORT WALK IN FREEZER PANELS
 CLASSIFIED IN ACCORDANCE WITH UL 1715 TO DOCUMENT NO
 FIRE SPRINKLERS REQUIRED. THANK YOU.
 COMMENT FROM 2ND REVIEW. THE FLOOR PLAN SHEET A1 SHOWS
 THIS A BUILDING TYPE VB NON-SPRINKLERED BUILDING. SHOWS
 VARIOUS WALK IN COOLERS AND FREEZERS. PLEASE NOTE THEY
 WILL REQUIRE A SEPARATE PERMIT. THE ISSUE IS THIS IS A
 NON-SPRINKLERED BUILDING. PLEASE REVIEW THE 2014 FBC-B
 2603.4.1.2 (4)COOLERS AND FREEZER WALLS.
 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1. WHERE THE COOLER OR
 FREEZER IS WITHIN A BUILDING, BOTH THE COOLER OR
 FREEZER AND THAT PART OF THE BUILDING IN WHICH IT IS
 LOCATED SHALL BE SPRINKLERED.
  
 THE EXCEPTION TO THIS IS FOUND UNDER SECTION 2603.4.1.3
 WALK-IN COOLERS. IN NON-SPRINKLERED BUILDINGS, FOAM
 PLASTIC HAVING A THICKNESS THAT DOES NOT EXCEED 4
 INCHES (102 MM) AND A MAXIMUM FLAME SPREAD INDEX OF 75
 IS PERMITTED IN WALK-IN COOLERS OR FREEZER UNITS WHERE
 THE AGGREGATE FLOOR AREA DOES NOT EXCEED 400 SQUARE
 FEET (37 M2) AND THE FOAM PLASTIC IS COVERED BY A METAL
 FACING NOT LESS THAN 0.032-INCH-THICK (0.81 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A MINIMUM
 BASE METAL THICKNESS OF 0.016 INCH (0.41 MM). A
 THICKNESS OF UP TO 10 INCHES (254 MM) IS PERMITTED
 WHERE PROTECTED BY A THERMAL BARRIER.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
  