| Plan Review Notes For Permit 15100991 |
| Permit Number |
15100991 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-17 14:53:38 | | | | 2ND REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1.CIVIL DRAWINGS ARE MARKED NOT APPROVED FOR | | | CONSTRUCTION PLEASE CLARIFY. | | | PER WPB AMEND. TO FBC SEC.107.2.1 | | | 2. SHT. C8NOTE ON SANITARY SEWER READS 2IN SS FORCE | | | MAIN UPSTREAM OF LIFT STATION LOOKS LIKE A TYPO PLEASE | | | CORRECT. | | | PER WPB AMEND. TO FBC SEC.107.2.1 | | | 3. SEPARATE PERMIT REQUIRED FOR BACK FLOW ON WATER | | | MAINS. | | | 4.SHT.C-14 DETAIL FOR GREASE INTERCEPTOR DOES NOT MATCH | | | APPROVED DETAIL FROM CITY STANDARD DETAIL GS-7 . SHT. | | | P-1 YOU ARE SHOWING TWO DIFFERENT DETAILS FOR GREASE | | | INTERCEPTOR PLEASE CLARIFY IF USING HYDRO-MECHANICAL | | | PROVIDE MANUFACTURE CALCULATIONS. | | | PER WPB AMEND. TO FBC SEC.107.2.1 | | | 5. BACKFLOW REQUIRED ON POWQERWASHER WATER SUPPLY. | | | PER WPB AMEND. TO FBC SEC.107.2.1 | | | 6. SHT. P1 PLEASE INDICATE WHAT IS BEING DRAINED INTO | | | HUB DRAIN NEXT TO FOOD SERVICE WALK IN REFRIDGE, BEHIND | | | EWC AND OUTSIDE RETAI;L WALKIN REFRIDGE ,HUB DRAINS | | | SHALL COMPLY WITH FBC PL SEC 1002.4 | | | 7.PROVIDE MANUFACTURE SPECS ON SANITIZER EQUIPMENT. | | | PER WPB AMEND. TO FBC SEC.107.2.1 |
|