2016-02-22 09:50:162ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100991
 2/22/16
  
 1) THE SUBMITTED AC CALCULATIONS INDICATE THE PROJECT
 LOCATION AND DESIGN TEMPERATURES FOR ORLANDO, FLORIDA.
 PLEASE REVISE THE CALCULATIONS USING THE CORRECT WEST
 PALM BEACH LOCATION AND DESIGN TEMPERATURES.
 2) SHEET M3 & S1.1: AS NOTED ON THE THE MASTER BILT
 ROOFTOP MECHANICAL UNIT DETAIL, PLEASE PROVIDE
 STRUCTURAL DRAWINGS FOR THE CURB CONSTRUCTION, AND THE
 PIPE HOOD SHOWN ON M2.
 3) M3: INDICATE THE SIZE OF CADMIUM SCREWS TO BE USED
 FOR ATTACHING THE FAN TO EXHAUST FAN TO THE CURB.
 3) THE REVISED PLAN NOW IDICATES THE WALK-IN BOXES AND
 REFRIGERATION SYSTEMS TO BE DONE UNDER SEPARATE PERMIT,
 WHICH WOULD IMPLY THAT THE TOTAL VALUE FOR THAT PERMIT
 WILL BE LABOR, MATERIALS AND EQUIPMENT. PLEASE CLARIFY
 IF THE SEPARATE PERMIT WILL INCLUDE THE COST OF MASTER
 BILT UNIT, AND THE COST OF MOUNTING THE UNIT AND THE
 OTHER ROOFTOP REFRIGERATION CONDENSERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  