2016-02-09 16:49:43THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 THESE COMMENTS WERE PREVIOUSLY POSTED AS PROVISO AND
 REPOSTED FOR THIS REVIEW.
  
 1. THE EXTERIOR EMERGENCY SHUT-OFF IS LOCATED IN AN
 AREA THAT IS BLOCKED BY TABLES AND CHAIRS. THE SHUT-OFF
 SHALL BE MOVED TO A MORE VISABLE AND ACCESSIBLE AREA
 PER NFPA 30A, CHAPTER 6,
  
 6.7 EMERGENCY ELECTRICAL DISCONNECTS. FUEL DISPENSING
 SYSTEMS SHALL BE PROVIDED WITH ONE OR MORE CLEARLY
 IDENTIFIED EMERGENCY SHUTOFF DEVICES OR ELECTRICAL
 DISCONNECTS. SUCH DEVICES OR DISCONNECTS SHALL BE
 INSTALLED IN APPROVED LOCATIONS
 BUT NOT LESS THAN 6 M (20 FT) OR MORE THAN 30 M (100
 FT) FROM THE FUEL DISPENSING DEVICES THAT THEY SERVE.
 EMERGENCY SHUTOFF DEVICES OR ELECTRICAL DISCONNECTS
 SHALL DISCONNECT POWER TO ALL DISPENSING DEVICES; TO
 ALL REMOTE PUMPS SERVING THE DISPENSING DEVICES; TO ALL
 ASSOCIATED POWER, CONTROL, AND SIGNAL CIRCUITS; AND TO
 ALL OTHER ELECTRICAL EQUIPMENT IN THE HAZARDOUS
 (CLASSIFIED) LOCATIONS SURROUNDING THE FUEL DISPENSING
 DEVICES. WHEN MORE THAN ONE EMERGENCY SHUTOFF DEVICE OR
 ELECTRICAL DISCONNECT IS PROVIDED, ALL DEVICES SHALL BE
 INTERCONNECTED.RESETTING FROM AN EMERGENCY SHUTOFF
 CONDITION SHALL REQUIRE MANUAL INTERVENTION AND THE
 MANNER OF RESETTING SHALL BE APPROVED BY THE AUTHORITY
 HAVING JURISDICTION.
 EXCEPTION: INTRINSICALLY SAFE ELECTRICAL EQUIPMENT NEED
 NOT MEET THIS REQUIREMENT.
  
 6.7.1 AT ATTENDED MOTOR FUEL DISPENSING FACILITIES, THE
 DEVICES OR DISCONNECTS SHALL BE READILY ACCESSIBLE TO
 THE ATTENDANT.
  
 6.7.2 AT UNATTENDED MOTOR FUEL DISPENSING FACILITIES,
 THE DEVICES OR DISCONNECTS SHALL BE READILY ACCESSIBLE
 TO PATRONS AND AT LEAST ONE ADDITIONAL DEVICE OR
 DISCONNECT SHALL BE READILY ACCESSIBLE TO EACH GROUP OF
 DISPENSING DEVICES ON AN INDIVIDUAL ISLAND.
  
 2. SHEET A 4 - PER FLORIDA 69A-60.0081; NOTICE SIGNAGE
 IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 THIS STRUCTURE REQUIRES A "R" SIGN.
  
 3. SHEET A 1 - THE LOCKS ON DOORS V1 AND V2 SHALL
 COMPLY WITH NFPA 101 CHAPTER 7 - A THUMB TURN LOCK IS
 NOT PERMITTED ON THE MAIN ENTRY DOOR(S). IN LIEU OF
 PANIC HARDWARE, THE MAIN ENTRY IS PERMITTED TO BE
 EQUIPPED WITH A KEYED LOCK WITH LOCK/UNLOCK INDICATOR
 WINDOW AND SIGNAGE STATING THE DOOR IS TO REMAIN
 UNLOCKED DURING BUSINESS HOURS. NO OTHER LOCKING OR
 LATCHING MECHANISMS ARE PERMITTED.
  
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEY-OPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET.
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY. ( IT IS
 PERMITTED UNDER CHAPTER 38, NEWBUSINESS OCCUPANCY, FOR
 PRINCIPAL ENTRANCE EXIT DOORS.)
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. HIGH ON A CONTRASTING BACKGROUND THAT READS
 AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF.
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
 SHOULD ALL OF THE ABOVE NOT BE POSSIBLE:
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.10 A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF WITH NOT MORE THAN ONE RELEASING OPERATION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  