| 2015-11-23 13:54:10 | ROOFING PLAN REVIEW |
| | W. P. B. PERMIT: 15100991 WAWA CONVENIENCE STORE |
| | ADD: 1520 BELVEDERE RD. |
| | CONT: TBD( TO BE DETERMINED) |
| | TEL: 407-661-9100 X2462 |
| | E-MAIL: [email protected] |
| | |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV. 23/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE FRONT COVER SHEET LIST 6 PRODUCT APPROVALS TO BE |
| | INSTALLED AT THIS JOBSITE LOCATION. PLEASE NOTE TO |
| | SUBMIT THE FLORIDA APPROVAL NUMBER WITH THE REPORTS. |
| | THE DUTCH SEAM METAL ROOFING REPORT DOES NOT SHOW UP ON |
| | THE FLORIDA PRODUCT APPROVAL WEBSITE. IF THERE IS NO |
| | FLORIDA APPROVAL YOU WILL NEED TO SUBMIT FOR EITHER A |
| | LOCAL APPROVAL OR FOR A SITE SPECIFIC APPROVAL. FLORIDA |
| | APPROVALS DO NOT START WITH MRD. THEY HAVE A FL NUMBER. |
| | |
| | SECTION 1707 ALTERNATIVE TEST PROCEDURE |
| | 1707.1 GENERAL. IN THE ABSENCE OF APPROVED RULES OR |
| | OTHER APPROVED STANDARDS, THE BUILDING OFFICIAL SHALL |
| | MAKE, OR CAUSE TO BE MADE, THE NECESSARY TESTS AND |
| | INVESTIGATIONS; OR THE BUILDING OFFICIAL SHALL ACCEPT |
| | DULY AUTHENTICATED REPORTS FROM APPROVED AGENCIES IN |
| | RESPECT TO THE QUALITY AND MANNER OF USE OF NEW |
| | MATERIALS OR ASSEMBLIES AS PROVIDED FOR IN SECTION |
| | 104.11. THE COST OF ALL TESTS AND OTHER INVESTIGATIONS |
| | REQUIRED UNDER THE PROVISIONS OF THIS CODE SHALL BE |
| | BORNE BY THE APPLICANT. |
| | |
| | 2A) BELOW IS A LIST OF COMPONENTS AND CLADDING FOR |
| | PRODUCT APPROVALS THAT CAN BE SUBMITTED NOW OR MAY BE |
| | CONSIDERED A DEFERRED SUBMITTAL (107.3.4.2.) 2010 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES,R-40 ROOF TOP |
| | INSULATION, ASSEMBLIES FOR FLAT & SLOPED, ROOF TOP |
| | CURBS, ROOF TOP INTAKE & EXHAUST FANS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 2B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 3) NO FLAT ROOF PRODUCT APPROVAL, ROOF TOP CURBS, ROOF |
| | TOP INTAKE & EXHAUST FANS NOR PRE-ENGINEERED A/C STANDS |
| | WERE SUBMITTED. |
| | |