| Plan Review Notes For Permit 15100991 |
| Permit Number |
15100991 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-09 16:43:50 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100991 | | | 11/9/15 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN | | | ACCORDANCE WITH THE ASHRAE/ACCA STANDARD 183 OR ACCA | | | MANUAL N- REFER TO SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | 2) THE COMPLIANCE DATA FOR THE AC SYSTEMS LISTED IN THE | | | ENERGY CALCULATION FORM 506-2014 DOES NOT MATCH THE | | | DATA IN THE AC SCHEDULE ON SHEET M3: PLEASE CORRECT. | | | 3) M3: CORRECT THE CFM/SF O/A CALCULATION FOR THE | | | RETAIL AREAS IN THE SCHEDULE PER TABLE 403.3: 0.12 CFM | | | PER SF. | | | 4) THE SUBMITTED RTU ROOF CURB CLIP CALCULATIONS ARE | | | BASED ON THE OUTDATED 2010 FBC AND DO NOT HAVE ORIGINAL | | | SIGNATURES AND SEALS FROM THE ENGINEER OF RECORD- REFER | | | TO SECTION 61G15-23.002 FAC AND PROVIDE ORIGINAL SIGNED | | | AND SEALED COPIES. PLEASE NOTE THAT THE CLIP CALCS SHOW | | | MECHANICAL ATTACHMENTS FOR THE CURBS AND RTU'S, HOWEVER | | | THE PLANS INDICATE WELDED ATTACHMENTS. PROVIDE | | | DOCUMENTATION OF APPROVAL FOR THIS TYPE OF CONNECTION | | | FROM THE AC MANUFACTURER. | | | 5) A SEPARATE PERMIT IS REQUIRED FOR THE WALK-IN BOXES | | | AND REFRIGERATION SYSTEMS. PLEASE PLACE A NOTE ON THE | | | PLAN ACCORDINGLY AND ADJUST THE VALUATION TO EXCLUDE | | | THIS PART OF THE PROJECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|