2015-11-09 16:43:501ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100991
 11/9/15
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH THE ASHRAE/ACCA STANDARD 183 OR ACCA
 MANUAL N- REFER TO SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
 2) THE COMPLIANCE DATA FOR THE AC SYSTEMS LISTED IN THE
 ENERGY CALCULATION FORM 506-2014 DOES NOT MATCH THE
 DATA IN THE AC SCHEDULE ON SHEET M3: PLEASE CORRECT.
 3) M3: CORRECT THE CFM/SF O/A CALCULATION FOR THE
 RETAIL AREAS IN THE SCHEDULE PER TABLE 403.3: 0.12 CFM
 PER SF.
 4) THE SUBMITTED RTU ROOF CURB CLIP CALCULATIONS ARE
 BASED ON THE OUTDATED 2010 FBC AND DO NOT HAVE ORIGINAL
 SIGNATURES AND SEALS FROM THE ENGINEER OF RECORD- REFER
 TO SECTION 61G15-23.002 FAC AND PROVIDE ORIGINAL SIGNED
 AND SEALED COPIES. PLEASE NOTE THAT THE CLIP CALCS SHOW
 MECHANICAL ATTACHMENTS FOR THE CURBS AND RTU'S, HOWEVER
 THE PLANS INDICATE WELDED ATTACHMENTS. PROVIDE
 DOCUMENTATION OF APPROVAL FOR THIS TYPE OF CONNECTION
 FROM THE AC MANUFACTURER.
 5) A SEPARATE PERMIT IS REQUIRED FOR THE WALK-IN BOXES
 AND REFRIGERATION SYSTEMS. PLEASE PLACE A NOTE ON THE
 PLAN ACCORDINGLY AND ADJUST THE VALUATION TO EXCLUDE
 THIS PART OF THE PROJECT.
  