2015-11-18 17:28:34THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET A 4 - PER FLORIDA 69A-60.0081; NOTICE SIGNAGE
 IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 THIS STRUCTURE REQUIRES A "R" SIGN.
  
 2. SHEET E 1 - THE INDICATED LOCATION OF THE OUTSIDE
 EMEGERNCY SHUT OFF SWITCH IS NOT APPROVED. THE AREA
 INDICATED IS NOT CLEARLY IDENTIFIED BEHIND SEATING AND
 TABLES AND NEXT TO A TRASH CAN. AN ALTENATIVE LOCATION
 SHALL BE COORDINATED WITH THE FIRE MARSHAL'S OFFICE.
 PALCING IT NEXT TO THE FRONT DOORS IS RECOMMENDEDAND AS
 LONG AS IT IS NOT LESS THAN 20FT OR MORE THAN 100FT
 FROM THE FUEL DISPENSING DEVICES IT SERVES; NO
 DIMENSIONS ARE PROVIDED.
  
 3. SHEET E 9 - A CLASS A NFPA 72 COMPLIANT MONITORED
 FIRE ALARM SYSTEM IS REQUIRED FOR THIS STRUCTURE.
 SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 4. SHEET A 1 - THE LOCKS ON DOORS V1 AND V2 SHALL
 COMPLY WITH NFPA 101 CHAPTER 7 - A THUMB TURN LOCK IS
 NOT PERMITTED ON THE MAIN ENTRY DOOR(S). IN LIEU OF
 PANIC HARDWARE, THE MAIN ENTRY IS PERMITTED TO BE
 EQUIPPED WITH A KEYED LOCK WITH LOCK/UNLOCK INDICATOR
 WINDOW AND SIGNAGE STATING THE DOOR IS TO REMAIN
 UNLOCKED DURING BUSINESS HOURS. NO OTHER LOCKING OR
 LATCHING MECHANISMS ARE PERMITTED.
  
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEY-OPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET.
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY. ( IT IS
 PERMITTED UNDER CHAPTER 38, NEWBUSINESS OCCUPANCY, FOR
 PRINCIPAL ENTRANCE EXIT DOORS.)
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. HIGH ON A CONTRASTING BACKGROUND THAT READS
 AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF.
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
 SHOULD ALL OF THE ABOVE NOT BE POSSIBLE:
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.10 A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF WITH NOT MORE THAN ONE RELEASING OPERATION.
  