| 2015-11-18 17:28:34 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | 1. SHEET A 4 - PER FLORIDA 69A-60.0081; NOTICE SIGNAGE |
| | IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | THIS STRUCTURE REQUIRES A "R" SIGN. |
| | |
| | 2. SHEET E 1 - THE INDICATED LOCATION OF THE OUTSIDE |
| | EMEGERNCY SHUT OFF SWITCH IS NOT APPROVED. THE AREA |
| | INDICATED IS NOT CLEARLY IDENTIFIED BEHIND SEATING AND |
| | TABLES AND NEXT TO A TRASH CAN. AN ALTENATIVE LOCATION |
| | SHALL BE COORDINATED WITH THE FIRE MARSHAL'S OFFICE. |
| | PALCING IT NEXT TO THE FRONT DOORS IS RECOMMENDEDAND AS |
| | LONG AS IT IS NOT LESS THAN 20FT OR MORE THAN 100FT |
| | FROM THE FUEL DISPENSING DEVICES IT SERVES; NO |
| | DIMENSIONS ARE PROVIDED. |
| | |
| | 3. SHEET E 9 - A CLASS A NFPA 72 COMPLIANT MONITORED |
| | FIRE ALARM SYSTEM IS REQUIRED FOR THIS STRUCTURE. |
| | SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, |
| | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU |
| | PRIOR TO ANY INSTALLATION. |
| | |
| | 4. SHEET A 1 - THE LOCKS ON DOORS V1 AND V2 SHALL |
| | COMPLY WITH NFPA 101 CHAPTER 7 - A THUMB TURN LOCK IS |
| | NOT PERMITTED ON THE MAIN ENTRY DOOR(S). IN LIEU OF |
| | PANIC HARDWARE, THE MAIN ENTRY IS PERMITTED TO BE |
| | EQUIPPED WITH A KEYED LOCK WITH LOCK/UNLOCK INDICATOR |
| | WINDOW AND SIGNAGE STATING THE DOOR IS TO REMAIN |
| | UNLOCKED DURING BUSINESS HOURS. NO OTHER LOCKING OR |
| | LATCHING MECHANISMS ARE PERMITTED. |
| | |
| | 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED |
| | TO HAVE KEY-OPERATED LOCKS FROM THE EGRESS SIDE, |
| | PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET. |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR THE SPECIFIC OCCUPANCY. ( IT IS |
| | PERMITTED UNDER CHAPTER 38, NEWBUSINESS OCCUPANCY, FOR |
| | PRINCIPAL ENTRANCE EXIT DOORS.) |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. HIGH ON A CONTRASTING BACKGROUND THAT READS |
| | AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF. |
| | THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS |
| | OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE BUILDING WHEN IT IS LOCKED. |
| | SHOULD ALL OF THE ABOVE NOT BE POSSIBLE: |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS |
| | OCCUPIED. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | 7.2.1.5.10 A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS |
| | AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY |
| | OPERATED UNDER ALL LIGHTING CONDITIONS. |
| | 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE |
| | DOOR LEAF WITH NOT MORE THAN ONE RELEASING OPERATION. |
| | |