| 2015-12-29 15:06:38 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1. THERE DOES NOT APPEAR TO BE LIGHTING CONTROL FOR THE |
| | TRASH COMPOUND LIGHTING. MANDATORY LIGHTING CONTROLS AS |
| | REQUIRED BY FBC-E. |
| | 2. ON SEVERAL OCCASIONS YOU REFER TO THE CIVIL DRAWING |
| | FOR REFERENCE. I WAS UNABLE TO LOCATE THE REFERENCED |
| | CIVIL DRAWING. YOU SHALL PROVIDE A SITE PLAN INDICATING |
| | THE LOCATION OF THE TRASH COMPOUND AND CANOPY WITH |
| | RELATION TO THE RETAIL BLDG. THIS WILL ALLOW FOR THE |
| | PROPER PLACEMENT OF THE EMERGENCY SHUT OFF REQUIRED BY |
| | NEC 514.11. |
| | 3. THE GENERAL NOTES ON SHEET E1 REFER TO THE 2008 |
| | EDITION OF THE NEC WHEN THE EDITION IN FORCE FOR THIS |
| | PROJECT IS THE 2011. CORRECT THE NOTE ACCORDINGLY. |
| | 4. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| | DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| | ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| | LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| | CONSIDERED ACCESSIBLE TO PEDESTRIANS. REVISE YOUR PLANS |
| | TO INCLUDE THE REQUIRED SIGN OUTLETS. |
| | 5. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE |
| | OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A |
| | SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION |
| | THEREOF AREA MEASURED HORIZONTALLY. THOUGH YOU DO |
| | INDICATE SHOW WINDOW OUTLETS, THE PLACEMENT AND |
| | QUANTITIES DO NOT MEET THE MINIMUM CODE REQUIREMENTS. |
| | 6. NEC 210.8(B) GROUND FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION REQUIRED FOR ALL ROOFTOP OUTLETS. THE |
| | OUTLETS SHOWN DO NOT COMPLY, REVISE PLANS ACCORDINGLY. |
| | 7. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| | AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| | LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| | WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| | 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING |
| | RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| | ?WR?. |
| | 8. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLETS. A 125 |
| | VOLT, SINGLE-PHASE, 15 OR 20 AMPERE-RATED RECEPTACLE |
| | OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR |
| | THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL |
| | BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT. ADDITIONAL |
| | ROOFTOP OUTLETS ARE REQUIRED TO COMPLY. |
| | 9. ALL SHOW WINDOW AND SIGN OUTLETS SHALL BE CONNECTED |
| | VIA THE LIGHTING CONTACTOR FOR COMPLIANCE WITH FBC-E. |
| | 10. NEC 760.41(B) THE BRANCH CIRCUIT SUPPLYING FIRE |
| | ALARM EQUIPMENT SHALL SUPPLY NO OTHER LOADS AND BE |
| | PERMANENTLY MARKED IN RED AND IDENTIFIED AS: "FIRE |
| | ALARM CIRCUIT? AND BE ACCESSIBLE ONLY TO QUALIFIED |
| | PERSONNEL. CIRCUIT 12 OF RPU, FIRE ALARM CIRCUIT SHALL |
| | COMPLY. |
| | 11. ALL BACKGROUND MUSIC SHALL BE AUTOMATICALLY MUTED |
| | IN THE EVENT OF A FIRE ALARM CONDITION. |
| | 12. FIRE ALARM WORK SHALL BE CONDUCTED UNDER A SEPARATE |
| | PERMIT AND SUBMITTAL. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |