2015-11-23 13:50:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100991 WAWA CONVENIENCE STORE
 ADD: 1520 BELVEDERE RD.
 CONT: TBD( TO BE DETERMINED)
 TEL: 407-661-9100 X2462
 E-MAIL: [email protected]
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 23/2015
 ACTION: DENIED
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS
  
 2) MISSING FROM PLANS SITE PLAN. 2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION. 107.2.5 SITE
 PLAN. / 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS.
 (1.) SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
  
 3) MISSING FROM PLAN REVIEW SOILS REPORT THE AREA IS IN
 A QUESTIONABLE SOIL ZONE . 2014 FLORIDA BUILDING CODE W
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION. 107.3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.
 (8.) STRUCTURAL REQUIREMENTS SHALL INCLUDE: SOIL
 CONDITIONS/ANALYSIS
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 4) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: 7.)
 FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION STEEL STRUCTURE WHERE EITHER
 STEEL IS WELDED OR BOLTED TOGETHER.
  
 4A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT. FORMS WERE SENT TO: : [email protected] MON.
 NOV. 23/2015 @ 08:14 AM.
  
 4B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT: KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 4C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 4D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 4E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 5) SUBMITTAL: ROOF CURB CLIP CALCULATIONS BY THOMAS
 RETSECK P. E. FL. # 46462
 5A) THE SUBMITTALS FOR ROOF CURB CLIP CALCULATIONS BY
 THOMAS RETSECK P. E. FL. # 46462 ARE COPIES, NOT
 ORIGINALLY SIGNED & SEALED. 61G15-23.002(2) FL. ADMIN.
 CODE.
  
 5B) THE SUBMITTALS FOR ROOF CURB CLIP CALCULATIONS BY
 THOMAS RETSECK P. E. FL. # 46462 HAVE NUMBERED SHEETS
 WITHIN THIS REPORT THAT APPEAR TO BE PULLED FROM MORE
 THAN DOCUMENT. THE PAGE NUMBERS ARE FROM WHAT APPEARS
 DIFFERENT DOCUMENTS. NOT ALL SHEETS ARE SIGNED NOR
 SEALED NOR IS THERE AN INDEX ON THE COVER SHEET
 INDICATING HOW MANY SHEETS ARE WITHIN THE SIGNED AND
 SEALED DOCUMENT. THE INDEX SHEET IS NOT SIGNED NOR
 SEALED. 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET
 OR INDEX SHEET.
  
 5C) THE SUBMITTALS FOR ROOF CURB CLIP CALCULATIONS BY
 THOMAS RETSECK P. E. FL. # 46462 INDICATES THIS DESIGN
 WAS UNDER THE 2010 FBC-B . LABELED SHEET 2 INDICATES
 CALCULATIONS PER THE 2010 FLORIDA BUILDING CODE AND
 REFERENCES WIND FORCES PER 1609 VW= 170 MPH. UNDER THE
 2010 FBC-B WE WERE UNDER A 140 MPH WIND ZONE VASD, 3
 SECOND GUST. NOT THE 170 VULT AS THE CURRENT 2014
 FBC-B, PLEASE CORRECT CODE ANALYSIS AND CALCULATIONS.
  
 6) THE FRONT COVER SHEET LIST 6 PRODUCT APPROVALS TO BE
 INSTALLED AT THIS JOBSITE LOCATION. PLEASE NOTE TO
 SUBMIT THE FLORIDA APPROVAL NUMBER WITH THE REPORTS.
 THE DUTCH SEAM METAL ROOFING REPORT DOES NOT SHOW UP ON
 THE FLORIDA PRODUCT APPROVAL WEBSITE. IF THERE IS NO
 FLORIDA APPROVAL YOU WILL NEED TO SUBMIT FOR EITHER A
 LOCAL APPROVAL OR FOR A SITE SPECIFIC APPROVAL. FLORIDA
 APPROVALS DO NOT START WITH MRD. THEY HAVE A FL NUMBER.
  
 SECTION 1707 ALTERNATIVE TEST PROCEDURE
 1707.1 GENERAL. IN THE ABSENCE OF APPROVED RULES OR
 OTHER APPROVED STANDARDS, THE BUILDING OFFICIAL SHALL
 MAKE, OR CAUSE TO BE MADE, THE NECESSARY TESTS AND
 INVESTIGATIONS; OR THE BUILDING OFFICIAL SHALL ACCEPT
 DULY AUTHENTICATED REPORTS FROM APPROVED AGENCIES IN
 RESPECT TO THE QUALITY AND MANNER OF USE OF NEW
 MATERIALS OR ASSEMBLIES AS PROVIDED FOR IN SECTION
 104.11. THE COST OF ALL TESTS AND OTHER INVESTIGATIONS
 REQUIRED UNDER THE PROVISIONS OF THIS CODE SHALL BE
 BORNE BY THE APPLICANT.
  
 7A) BELOW IS A LIST OF COMPONENTS AND CLADDING FOR
 PRODUCT APPROVALS THAT CAN BE SUBMITTED NOW OR MAY BE
 CONSIDERED A DEFERRED SUBMITTAL (107.3.4.2.) 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES,R-40 ROOF TOP
 INSULATION, ASSEMBLIES FOR FLAT & SLOPED, ROOF TOP
 CURBS, ROOF TOP INTAKE & EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 7B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7C) PRODUCT APPROVALS DOORS, WINDOWS AND MULLIONS,
 PLEASE CIRCLE TO IDENTIFY WIDTH, HEIGHT, OF GLAZING.
 MULLIONS SIZE OF MULLION, LENGTH OF MULLION, IF
 RE-ENFORCED OR NOT, CIRCLE THE ASSOCIATED PRESSURES
 WITH THE TRIBUTARY AREA, AND THE FASTENERS TO BE
 INSTALLED.
  
 7D) NO FLAT ROOF PRODUCT APPROVAL, ROOF TOP CURBS, ROOF
 TOP INTAKE & EXHAUST FANS NOR PRE-ENGINEERED A/C STANDS
 WERE SUBMITTED.
  
 8) SHEET S-1 THE NEGATIVE PRESSURES FOR OPENINGS IN
 WALL ZONES 4 & 5 BOTH APPEAR TO BE A LITTLE LOW FOR
 130.1 VASD WITH A MEAN ROOF HEIGHT OF 17.83. 2014 FBC-B
 1603.1.4(5) WIND DESIGN DATA.
  
 9) SHEET A3 SHOWS A ROOF TOP MASTER BUILT CONDENSING
 UNIT DETAIL 6/ A3 SHOWS A CUT SECTION THROUGH THE
 RAISED EQUIPMENT CURB. THE STRUCTURAL SHEET S-4.1 SHOWS
 THE UNIT AND DETAILS 22 & 23 OF THE SAME S-4.1.
  
 9A) DETAIL # 23 SHOWS (3) CONTINUOUS 2X6 PT PLATES
 BEING ANCHORED TO THE B-DECK WITH # 10 TEK SCREWS @ 12
 INCHES ON CENTER MAXIMUM. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. THE PLAN DOES NOT STATE THE
 LENGTH OF THE TEK SCREWS? THE MAXIMUM OF 12 INCHES ON
 CENTER, DOES THIS MEAN 3 SCREWS ARE PUT IN EVERY 12
 INCHES ON CENTER? THE PLANS DO NOT CLEARLY INDICATE
 DOES THE TEK SCREWS ONLY GO THROUGH THE B DECK OR ARE
 THEY REQUIRED TO PENETRATE THE STEEL ANGLE THAT IS PART
 OF THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM).
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 9B) SAME DETAIL, THE (3) HORIZONTAL 2X6 PT BOTTOM PLATE
 SHOWS (3) 2X12 VERTICAL PT MEMBERS BEING ATTACHED TO
 THE TOP 2X6 PT MEMBER WITH # 10 WOOD SCREWS 12 INCHES
 ON CENTER. AGAIN THERE IS NO LENGTH OF THE SCREW? ).
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 9C) SAME DETAIL SHOWS A ? INCH PLYWOOD WOOD DECK
 ATTACHED WITH # 10 WOOD SCREWS MAXIMUM 12 INCHES ON
 CENTER. AGAIN THERE IS NO DIMENSION AS TO LENGTH. THERE
 ARE NO STRAPS TYING THE BOTTOM PLATE TO THE TOP. THERE
 IS ALSO NO DETAIL OF HOW THE MASTER BUILT CONDENSING
 UNIT WILL BE ANCHORED TO THE RAISED CURB. 2014 FBC- M-
 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
  