| Plan Review Notes For Permit 15100982 |
| Permit Number |
15100982 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-04 16:26:29 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) APPROVED BY THE | | | ARCHITECT OF RECORD FOR PEEL & STICK ROOF TILE | | | UNDERLAYMENT AS SPECIFIED ON PLANS. GRACE ICE & WATER | | | SHIELD NOA 12-1115.02 SUBMITTED CAN'T BE USED. IT SHALL | | | NOT BE USED AS ROOF TILE UNDERLAYMENT . SEE GENERAL | | | LIMITATION #10 ON LAST PAGE OF NOA SUBMITTED. | | | | | | NOTE: PROPERTY IS LOCATED IN FLOOD ZONE A5. FINISH | | | FLOOR ELEVATION AND EQUIPMENT NEED TO BE 6" ABOVE BASE | | | FLOOD ELEVATION. THE BASE FLOOD ELEVATIONS IS 7'-0". | | | ELEVATION CERTIFICATES ARE REQUIRED DURING | | | CONSTRUCTION. |
|