Plan Review Notes
Plan Review Notes For Permit 15100982
Permit Number 15100982
Review Stop P
Sequence Number 1
Notes
Date Text
2015-11-04 06:55:341) INDDICATE THE SIZE OF THE GUTTERS ON THE PLANS.
 SIZING SHALL COMPLY W/2014 FBC-PLUMBING TABLE 1106.6.
 2) DOWNSPOUTS SHALL DISCHARGE A MINIMUM OF 1 FOOT FROM
 THE STRUCTURE SIDEWALL PER FBC-RES. SEC.R318.5
 3) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT A WATER RISER FOR REVIEW. THE SANITARY AND
 WATER RISERS ARE BOTH REVIEWED AT THIS STAGE. THE GAS
 CAN BE A SEPARATE SUBMITTAL. WPB AMEND. TO FBC SEC.
 107.3.5.3.
 5) THE SHOWERS AND WATER CLOSETS IN THE BATHROOMS ARE
 NOT PROPERLY VENTED. CONNECT THE LAVATORY DRAIN TO THE
 HORIZONTAL DRAIN BETWEEN THE WATER CLOSEET AND THE
 SHOWER IN BOTH BATHROOMS. 2014 FBC-RES. SEC. P3101.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  