| Plan Review Notes For Permit 15100982 |
| Permit Number |
15100982 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-04 06:55:34 | 1) INDDICATE THE SIZE OF THE GUTTERS ON THE PLANS. | | | SIZING SHALL COMPLY W/2014 FBC-PLUMBING TABLE 1106.6. | | | 2) DOWNSPOUTS SHALL DISCHARGE A MINIMUM OF 1 FOOT FROM | | | THE STRUCTURE SIDEWALL PER FBC-RES. SEC.R318.5 | | | 3) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) SUBMIT A WATER RISER FOR REVIEW. THE SANITARY AND | | | WATER RISERS ARE BOTH REVIEWED AT THIS STAGE. THE GAS | | | CAN BE A SEPARATE SUBMITTAL. WPB AMEND. TO FBC SEC. | | | 107.3.5.3. | | | 5) THE SHOWERS AND WATER CLOSETS IN THE BATHROOMS ARE | | | NOT PROPERLY VENTED. CONNECT THE LAVATORY DRAIN TO THE | | | HORIZONTAL DRAIN BETWEEN THE WATER CLOSEET AND THE | | | SHOWER IN BOTH BATHROOMS. 2014 FBC-RES. SEC. P3101.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|