| 2015-11-10 13:23:55 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. PER NEC 230.2 AND CITY OF WEST PALM BEACH |
| | AMENDMENTS, YOU ARE ONLY PERMITTED TO HAVE A SINGLE |
| | SERVICE AND A SINGLE METER TO THE PROPERTY. REVISE YOUR |
| | DRAWINGS ACCORDINGLY. IF THE SERVICE WILL BE ON THE |
| | MAIN HOUSE, PROVIDE A SITE PLAN (NTS) INDICATING WHERE |
| | THE SERVICE WILL BE/IS. ON THE SITE PLAN INDICATE THE |
| | LOCATION OF ALL THE SUB-PANELS MAKING SURE TO GROUP ALL |
| | THE DISCONNECTS AS INDICATED IN NEC 230.72. |
| | 2. NEC 215.5, YOU CURRENTLY HAVE A FEEDER DIAGRAM WITH |
| | PROPER LOAD CALCS, BUT THAT WILL/MAY CHANGE WITH THE |
| | REVISION OF THE SERVICE. PROVIDE A SITE SPECIFIC FEEDER |
| | DIAGRAM WITH THE LOAD CALCS AND CONDUCTOR SIZING AS |
| | INDICATED. |
| | 3. NEC 408.4, YOU CURRENTLY HAVE A CIRCUIT DIRECTORY AS |
| | REQUIRED HEREIN BUT IF ANY CHANGES OCCUR AS A RESULT OF |
| | THE REVISION, CORRECT ACCORDINGLY. INDICATE ON EACH |
| | PANEL THE LOCATION OF THE POWER SOURCE (ELECTRIC FEED). |
| | 4. NEC 314.27(A)(2) REQUIRES THAT ALL CEILING OUTLETS |
| | USED FOR LUMINAIRES BE RATED TO SUPPORT 50#. |
| | 5. NEC 314.27(C) REQUIRES THAT THOSE BOXES INTENDED TO |
| | SUPPORT PADDLE FANS BE LISTED FOR THE PURPOSE. |
| | 6. NEC 406.12 REQUIRES THAT ALL NON-LOCKING 125 V. 15 ? |
| | 20 AMP RECEPTACLES IN DWELLING UNITS ARE LISTED |
| | TAMPER-RESISTANT ?TR?. |
| | 7. NEC 406.9 REQUIRES THAT ALL RECEPTACLES IN WET |
| | LOCATIONS BE LISTED WEATHER RESISTANT ?WR? IN ADDITION |
| | TO THE GFI AND WP COVERS. CORRECT ELECTRICAL NOTES 25 |
| | ACCORDINGLY. |
| | 8. FBC-ENERGY CONSERVATION R402.4.4 STATES THAT ALL |
| | RECESSED LUMINARIES INSTALLED IN THE BLDG. THERMAL |
| | ENVELOPE BE IC RATED AND SEALED TO LIMIT THE TRANSFER |
| | OF AIR BETWEEN THE CONDITIONED AND THE NON-CONDITIONED |
| | SPACE. |
| | 9. NEC 440.11, REQUIRES THAT YOU HAVE A DISCONNECT FOR |
| | THE AIR HANDLER/HEATER. |
| | 10. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO |
| | IDENTIFY A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT |
| | A TYPE OF CABLE; REFER TO CABLE TYPES ?NM?, ?NMC? OR |
| | ?NMS?. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |