Plan Review Notes
Plan Review Notes For Permit 15100982
Permit Number 15100982
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-20 19:02:15NEW POOL CABANA (R3) BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". SEC.
 R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 REVISE WIND LOAD INFORMATION AND COMPONENTS AND
 CLADDING DESIGN PRESSURES SHEET S-1.02. ALSO, REVISE
 THE WINDOWS AND DOOR DESIGN PRESSURES ON SHEET A-2.01.
  
 2- SPECIFY FIREBLOCKING IN ALL WALL SECTIONS SHOWN ON
 SHEET A-3.02 AS REQUIRED BY SEC. R302.11 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FIRE RATED SOFFIT (SOUTH SIDE) AS REQUIRED BY TABLE
 R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- TYPICAL WALL SECTION ON SHEET A-3.02: SHOW
 COMPLIANCE WITH THE 6" CLEARANCE FROM GRADE TO WALL
 COVERING AS REQUIRED BY SEC. R318.7 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES. VALUATION WAS UPDATED TO $112,650.
 THE PERMIT FEE BALANCE IS $2385.63.
  
 6- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- PROVIDE SOIL TEST REPORT WITH ENGINEER'S ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. AND
 PROVIDE 2 COPIES. ONLY ONE WAS PROVIDED A THIS TIME.
  
 8- ENERGY CALCULATIONS SUBMITTED;
 A) REVISE THE CEILING R-VALUE TO MATCH PLANS. SEC.
 R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH
 PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 C) PROVIDE THE OWNER AND BUILDER INFORMATION. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT
 USING THE DEFAULT FACTOR FOR GLAZING.
  
 9- PROVIDE ICC EVALUATION REPORT FOR THE SPRAY FOAM
 INSULATION SPECIFIED ON SHEET A-3.02. DESIGNER OF
 RECORD TO REVIEW AND APPROVE THE REPORT IN WRITING
 PRIOR TO SUBMITTAL TO THIS OFFICE. SEC. R316 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 10- NEED TO SPECIFY ATTIC ACCESS SIZE AND LOCATION AS
 REQUIRED BY SEC. R807 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). NOTE: NEED ONE ATTIC ACCESS ON EACH ROOF AREA.
 ONE IN POOL ROOM, ONE IN HOME OFFICE AND ONE IN YOGA
 ROOM.
  
 11- NEED TO SPECIFY THE ATTIC LIVE LOAD AS REQUIRED BY
 FOOTNOTES "B" AND "G" OF TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE ADHESIVE AS SPECIFIED ON SHEET A-3.02. SEE
 CONCRETE TILE NOA SUBMITTED FOR LISTED ADHESIVE.
  
 B) PEEL & STICK ROOF TILE UNDERLAYMENT AS SPECIFIED ON
 SHEET A-3.02.
  
 C) SLIDING GLASS DOORS. DRAWINGS SUBMITTED WITH NOA
 12-0820.09 ARE INCOMPLETE. PROVIDE COMPLETE DRAWINGS.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR DESIGNER OF RECORD TO LIST
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED
 CONNECTORS.
  
 E) ALUMINUM LOUVERS AS SHOWN ON THE EXTERIOR
 ELEVATIONS. AND, PROVIDE COMPLETE INSTALLATION
 SPECIFICATIONS.
  
 F) COLONIAL SHUTTERS AS SHOWN ON THE EXTERIOR
 ELEVATIONS. AND PROVIDE COMPLETE INSTALLATION SCHEDULE.
 SEE CITY SAMPLE FOR SHUTTERS INSTALLATION OR PROVIDE
 COMPLETE INFORMATION UNDER A DIFFERENT FORMAT.
  
 13- DESIGNER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- FOR YOUR INFORMATION THIS PROPERTY IS LOCATED IN
 FLOOD ZONE A5. FINISH FLOOR ELEVATION AND EQUIPMENT
 NEED TO BE 6" ABOVE BASE FLOOD ELEVATION. THE BASE
 FLOOD ELEVATIONS ISA 7'-0". ELEVATION CERTIFICATES ARE
 REQUIRED DURING CONSTRUCTION SHOWING 7'-6" MIN. FINISH
 FLOOR ELEVATION. PLEASE CONTACT SAMANTHA HILL
 (561)805-6724 FOR ELEVATION CERTIFICATES REVIEW AND
 COORDINATION TO AVOID CONFLICTS OR DELAYS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. SUBMITT OLD COPIES
 FOR REFERENCE. PLEASE DON'T STAPPLE OLD COPIES TO THE
 NEW SET OF PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]