| 2015-11-20 19:02:15 | NEW POOL CABANA (R3) BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". SEC. |
| | R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | REVISE WIND LOAD INFORMATION AND COMPONENTS AND |
| | CLADDING DESIGN PRESSURES SHEET S-1.02. ALSO, REVISE |
| | THE WINDOWS AND DOOR DESIGN PRESSURES ON SHEET A-2.01. |
| | |
| | 2- SPECIFY FIREBLOCKING IN ALL WALL SECTIONS SHOWN ON |
| | SHEET A-3.02 AS REQUIRED BY SEC. R302.11 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | FIRE RATED SOFFIT (SOUTH SIDE) AS REQUIRED BY TABLE |
| | R302.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 4- TYPICAL WALL SECTION ON SHEET A-3.02: SHOW |
| | COMPLIANCE WITH THE 6" CLEARANCE FROM GRADE TO WALL |
| | COVERING AS REQUIRED BY SEC. R318.7 OF FBC-RESIDENTIAL, |
| | 5TH EDITION (2014). |
| | |
| | 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| | PROFESSIONAL FEES. VALUATION WAS UPDATED TO $112,650. |
| | THE PERMIT FEE BALANCE IS $2385.63. |
| | |
| | 6- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| | R401.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 7- PROVIDE SOIL TEST REPORT WITH ENGINEER'S ORIGINAL |
| | SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. AND |
| | PROVIDE 2 COPIES. ONLY ONE WAS PROVIDED A THIS TIME. |
| | |
| | 8- ENERGY CALCULATIONS SUBMITTED; |
| | A) REVISE THE CEILING R-VALUE TO MATCH PLANS. SEC. |
| | R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH |
| | PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | |
| | C) PROVIDE THE OWNER AND BUILDER INFORMATION. SEC. |
| | R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR |
| | AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS |
| | WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT |
| | USING THE DEFAULT FACTOR FOR GLAZING. |
| | |
| | 9- PROVIDE ICC EVALUATION REPORT FOR THE SPRAY FOAM |
| | INSULATION SPECIFIED ON SHEET A-3.02. DESIGNER OF |
| | RECORD TO REVIEW AND APPROVE THE REPORT IN WRITING |
| | PRIOR TO SUBMITTAL TO THIS OFFICE. SEC. R316 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 10- NEED TO SPECIFY ATTIC ACCESS SIZE AND LOCATION AS |
| | REQUIRED BY SEC. R807 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). NOTE: NEED ONE ATTIC ACCESS ON EACH ROOF AREA. |
| | ONE IN POOL ROOM, ONE IN HOME OFFICE AND ONE IN YOGA |
| | ROOM. |
| | |
| | 11- NEED TO SPECIFY THE ATTIC LIVE LOAD AS REQUIRED BY |
| | FOOTNOTES "B" AND "G" OF TABLE R301.5 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) ROOF TILE ADHESIVE AS SPECIFIED ON SHEET A-3.02. SEE |
| | CONCRETE TILE NOA SUBMITTED FOR LISTED ADHESIVE. |
| | |
| | B) PEEL & STICK ROOF TILE UNDERLAYMENT AS SPECIFIED ON |
| | SHEET A-3.02. |
| | |
| | C) SLIDING GLASS DOORS. DRAWINGS SUBMITTED WITH NOA |
| | 12-0820.09 ARE INCOMPLETE. PROVIDE COMPLETE DRAWINGS. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| | SPECIFIED CONNECTOR OR DESIGNER OF RECORD TO LIST |
| | FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED |
| | CONNECTORS. |
| | |
| | E) ALUMINUM LOUVERS AS SHOWN ON THE EXTERIOR |
| | ELEVATIONS. AND, PROVIDE COMPLETE INSTALLATION |
| | SPECIFICATIONS. |
| | |
| | F) COLONIAL SHUTTERS AS SHOWN ON THE EXTERIOR |
| | ELEVATIONS. AND PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | SEE CITY SAMPLE FOR SHUTTERS INSTALLATION OR PROVIDE |
| | COMPLETE INFORMATION UNDER A DIFFERENT FORMAT. |
| | |
| | 13- DESIGNER OF RECORD TO APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 14- FOR YOUR INFORMATION THIS PROPERTY IS LOCATED IN |
| | FLOOD ZONE A5. FINISH FLOOR ELEVATION AND EQUIPMENT |
| | NEED TO BE 6" ABOVE BASE FLOOD ELEVATION. THE BASE |
| | FLOOD ELEVATIONS ISA 7'-0". ELEVATION CERTIFICATES ARE |
| | REQUIRED DURING CONSTRUCTION SHOWING 7'-6" MIN. FINISH |
| | FLOOR ELEVATION. PLEASE CONTACT SAMANTHA HILL |
| | (561)805-6724 FOR ELEVATION CERTIFICATES REVIEW AND |
| | COORDINATION TO AVOID CONFLICTS OR DELAYS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE ANY REVISED SHEET. SUBMITT OLD COPIES |
| | FOR REFERENCE. PLEASE DON'T STAPPLE OLD COPIES TO THE |
| | NEW SET OF PLANS. |
| | |