Plan Review Notes
Plan Review Notes For Permit 15100912
Permit Number 15100912
Review Stop B
Sequence Number 2
Notes
Date Text
2015-11-12 07:24:25PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DETAIL FOR ANCHORING THE PANELS TO THE CONCRETE
 ROOF TILE IS NOT ACCEPTABLE. THERE IS NO WAY FOR THE
 INSPECTORS TO DETERMINE THAT THE CAVITIES UNDER THE
 TILE TO WHICH THE BRACKET IS ATTACHED OR THE FIVE TILES
 AROUND IT ARE FILLED COMPLETELY WITH DOW TILE BOND
 ADHESIVE OR EQUAL. CONCRETE ROOF TILE MAY BE ATTACHED
 MECHANICALLY AND WHEN ATTACHED WITH ADHESIVES THE
 CAVITIES ARE NOT FILLED COMPLETELY. THE PERSON THAT
 APPLIES THE ROOF TILE ADHESIVES IS REQUIRED TO BE
 TRAINED AND CERTIFIED BY THE MANUFACTURER. THERE IS NO
 TESTING TO SHOW THAT ATTACHING ANYTHING DIRECTLY TO
 CONCRETE ROOF TILE WITH SCREWS IS ACCEPTABLE. THERE IS
 NO ROOF TILE MANUFACTURER'S THAT WILL APPROVE THIS
 ATTACHMENT METHOD USING THEIR TILE AS THE ANCHOR
 SUBSTRATE. PROVIDE AN ANCHORING METHOD THAT USES A
 SUITABLE SUBSTRATE. FBC-R905.3.7
 THE ACCEPTABLE ALTERNATE THAT WAS CIRCLED ON THE
 DRAWING STATES "PROVIDE TAPCON SCREWS OF ADEQUATE
 LENGTH TO SECURE BRACKET TO CEMENT TILE".