| Plan Review Notes For Permit 15100912 |
| Permit Number |
15100912 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-29 19:09:48 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC. | | | THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE | | | 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT | | | DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC | | | FIFTH EDITION. | | | | | | 2) THE DETAIL FOR ANCHORING THE PANELS TO THE CONCRETE | | | ROOF TILE IS NOT ACCEPTABLE. THERE IS NO WAY FOR THE | | | INSPECTORS TO DETERMINE THAT THE CAVITIES UNDER THE | | | TILE TO WHICH THE BRACKET IS ATTACHED OR THE FIVE TILES | | | AROUND IT ARE FILLED COMPLETELY WITH DOW TILE BOND | | | ADHESIVE OR EQUAL. CONCRETE ROOF TILE MAY BE ATTACHED | | | MECHANICALLY AND WHEN ATTACHED WITH ADHESIVES THE | | | CAVITIES ARE NOT FILLED COMPLETELY. THE PERSON THAT | | | APPLIES THE ROOF TILE ADHESIVES IS REQUIRED TO BE | | | TRAINED AND CERTIFIED BY THE MANUFACTURER. THERE IS NO | | | TESTING TO SHOW THAT ATTACHING ANYTHING DIRECTLY TO | | | CONCRETE ROOF TILE WITH SCREWS IS ACCEPTABLE. THERE IS | | | NO ROOF TILE MANUFACTURER'S THAT WILL APPROVE THIS | | | ATTACHMENT METHOD USING THEIR TILE AS THE ANCHOR | | | SUBSTRATE. PROVIDE AN ANCHORING METHOD THAT USES A | | | SUITABLE SUBSTRATE. FBC-R905.3.7 | | | |
|