Plan Review Notes
Plan Review Notes For Permit 15100876
Permit Number 15100876
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-09 08:08:59REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH FBC-R308.4.5 GLAZING AND WET
 SURFACES. GLAZING IN WALLS, ENCLOSURES OR FENCES
 CONTAINING OR FACING HOT TUBS, SPAS, WHIRLPOOLS,
 SAUNAS, STEAM ROOMS, BATHTUBS, SHOWERS AND INDOOR OR
 OUTDOOR SWIMMING POOLS WHERE THE BOTTOM EXPOSED EDGE OF
 THE GLAZING IS LESS THAN 60 INCHES (1524 MM) MEASURED
 VERTICALLY ABOVE ANY STANDING OR WALKING SURFACE SHALL
 BE CONSIDERED A HAZARDOUS LOCATION. THIS SHALL APPLY TO
 SINGLE GLAZING AND ALL PANES IN MULTIPLE GLAZING.
 EXCEPTION: GLAZING THAT IS MORE THAN 60 INCHES (1524
 MM), MEASURED HORIZONTALLY AND IN A STRAIGHT LINE, FROM
 THE WATER?S EDGE OF A BATHTUB, HOT TUB, SPA, WHIRLPOOL,
 OR SWIMMING POOL.
  
 2) SHOW COMPLIANCE WITH FBC-R303.3 BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET, ONE-HALF OF
 WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST
 AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  