| 2015-11-09 08:08:59 | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SHOW COMPLIANCE WITH FBC-R308.4.5 GLAZING AND WET |
| | SURFACES. GLAZING IN WALLS, ENCLOSURES OR FENCES |
| | CONTAINING OR FACING HOT TUBS, SPAS, WHIRLPOOLS, |
| | SAUNAS, STEAM ROOMS, BATHTUBS, SHOWERS AND INDOOR OR |
| | OUTDOOR SWIMMING POOLS WHERE THE BOTTOM EXPOSED EDGE OF |
| | THE GLAZING IS LESS THAN 60 INCHES (1524 MM) MEASURED |
| | VERTICALLY ABOVE ANY STANDING OR WALKING SURFACE SHALL |
| | BE CONSIDERED A HAZARDOUS LOCATION. THIS SHALL APPLY TO |
| | SINGLE GLAZING AND ALL PANES IN MULTIPLE GLAZING. |
| | EXCEPTION: GLAZING THAT IS MORE THAN 60 INCHES (1524 |
| | MM), MEASURED HORIZONTALLY AND IN A STRAIGHT LINE, FROM |
| | THE WATER?S EDGE OF A BATHTUB, HOT TUB, SPA, WHIRLPOOL, |
| | OR SWIMMING POOL. |
| | |
| | 2) SHOW COMPLIANCE WITH FBC-R303.3 BATHROOMS. |
| | BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR |
| | ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN |
| | WINDOWS OF NOT LESS THAN 3 SQUARE FEET, ONE-HALF OF |
| | WHICH MUST BE OPENABLE. |
| | EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE |
| | ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE |
| | PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE |
| | DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST |
| | AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE |
| | OUTDOORS. |
| | |
| | 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |