| Notes |
| Date |
Text |
| 2015-10-27 13:37:11 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100875 | | | 10/27/15 | | | | | | 1) THE DESIGN PROFESSIONAL OF RECORD HAS NOT PROVIDED | | | COMPLETE WIND LOAD DESIGN CRITERIA, OR COMPLETE DETAILS | | | FOR INSTALLATION OF THE EXTERIOR EXHAUST FAN. REFER TO | | | SECTION R301.2.1, FBC-14 RESIDENTIAL AND REVISE THE | | | PLAN TO BE IN COMPLIANCE. PROVIDE THE FOLLOWING: A) | | | BASIC WIND SPEED, EXPOSURE CATEGORY, HEIGHT AND | | | ADJUSTMENT ADJUSTMENT COEEFICIENTS, DESIGN PRESSURES | | | ETC. | | | B) INDICATE THE TYPE, SIZE, AND QUANTITIES OF ANCHORS | | | FOR MOUNTING THE EXHAUST FAN TO THE WALL. | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE HOOD, | | | THE CHARBROILER, AND THE EXHAUST FAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|