Plan Review Notes
Plan Review Notes For Permit 15100870
Permit Number 15100870
Review Stop P
Sequence Number 2
Notes
Date Text
2015-12-18 13:40:101) ) LINT INTERCEPTORS SHALL COMPLY WITH 2014
 FBC-PLUMBING SEC.1003.6. PROVIDE SIZING CALCULATIONS
 FOR THE LINT INTERCEPTORS. WPB AMEND. TO FBC SEC.
 107.2.1, 107.3.5.1.3.
 2) SUBMIT A DETAIL AND SIZING CALCULATIONS FOR THE
 GREASE INTERCEPTORS. FACTORY SIZING CALCULATIONS DONE
 BY THE MANUFACTURER ARE REQUIRED FOR THE SIZING OF
 HYDROMECHANICAL GREASE INTERCEPTORS TO ENSURE PROPER
 SIZING.2014 FBC-PLUMBING SEC. 1003.2.
 3) PROVIDE THE PROPER MATCH LINES ON THE PLUMBING
 DRAWINGS. THERE ARE NO MATCH LINES ON THE TOP OF THE
 PAGES & SOME OF THE MATCH LINES DO NOT CORRELATE WITH
 EACH OTHER. CHECK ALL SHEETS.WPB AMEND. TO FBC SEC.
 107.2.1.
 4) SHT. IR1.00 - ALL THE NOTES ON THE IRRIGATION PLAN
 ARE ILLEGIBLE. CLARIFY.
 5) SUBMIT A DETAIL/SPECIFICATIONS FOR THE GREASE
 INTERCEPTORS UNDER THE SINKS.SIZING CALCULATIONS SHALL
 BE DONE IN ACCORDANCE WITH PDI STANDARD G101. FBC
 PLUMBING SEC. 1003.3.4.
 6) SHT. P0.03 - SUBMIT A DETAIL OF GREASE INTERCEPTOR
 GI-2 IF THAT INTERCEPTOR IS GOING TO BE USED.
 7) SUBMIT A DETAIL OF THE SOLIDS INTERCEPTOR FOR THE
 TEAM DUGOUTS. WPB AMEND. TO FBC SEC. 107.2.1.
 8) SHT.P2-101 - THE ELEVATOR SUMP CONNECTION TO THE
 DRAINAGE SYSTEM SHALL BE AN INDIRECT CONNECTION PER
 2014 FBC-PLUMBING, SEC.301.6
 9) PLUMBING SHEETS - LIST THE SPECIFIC SHEET NUMBER
 WHERE A NOTE STATES " SEE CIVIL DRAWINGS FOR
 CONTINUATION." OR "SEE ARCHITECTURAL DRAWINGS." WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) SHT. H1.00 - SEC. 1.02 - REQUIREMENTS - DELETE THE
 REFERENCE TO THE INTERNATIONAL BUILDING CODE AND INSERT
 THE 2014 FLORIDA BUILDING CODE.
 11) SHT.P6.02 - EMERGENCY OVERFLOW DRAIN DETAIL SHOWS
 THE OVERFLOW DRAINS TERMINATING FLUSH WITH THE WALL.
 THE OVERFLOW DRAINS SHALL DISCHARGE A MINIMUM OF ONE
 FOOT FROM THE BUILDING WALL PER THE 2014 FBC
 SEC.1503.7.
 12) THE NARRATIVE RESPONSE TO PREVIOUS COMMENT #18
 REFERS TO SHT.A2.150. THIS SHEET IS NOT INCLUDED IN
 THIS SUBMITTAL. CLARIFY.
 13) SHT.P2.101 - THERE IS AN ENLARGED PLAN DETAIL
 NUMBER 2/P2.111 REFERENCED ON THE PLAN BUT SHT. P2.111
 IS NOT IN THIS SET. CLARIFY.
 14) SHT.P2.101 - NUMBERED NOTES REFER TO A SAND/OIL
 INTERCEPTOR. SUBMIT A DETAIL AND SIZING CALCULATIONS
 AND ALSO SHOW THE LOCATION OF THE INTERCEPTOR ON THE
 PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 15) IF POSSIBLE, PLEASE PROVIDE THE ROOM NUMBERS OF THE
 AREAS ON THE PLUMBING DRAWINGS. IT WILL ASSIST ME IN MY
 REVIEW OF THE PLUMBING SYSTEM.
 16) SHT. P2.102 - SEE MATCH LINE TO SHT. P2.101 - THE
 STORM LINE ON P2.101 SHOWS A 15 INCH LINE AND P2.102
 SHOWS A 12 INCH LINE AND THE SQUARE FOOTAGES
 DIFFER.CLARIFY.
 17) SHT. P2108 - THERE ARE NO NUMBERED NOTES ON THE
 SHEET. CLARIFY.
 18) SHT. P2.102 - SEE MATCH LINE TO SHT. P2.101 - THERE
 IS A STORM LINE THAT GOES FROM 12" TO 18" AND THEN TO
 15" AND THEN TO 18" AND TO 15" AGAIN. CLARIFY.
 19) SUBMIT EXPANDED SANITARY RISERS FOR REVIEW. IT IS
 DIFFICULT TO DETERMINE WHERE ONE LINE STARTS AND ENDS
 AND SIZE ALL SECTIONS OF THE SANITARY RISERS.WPB AMEND.
 TO FBC SEC. 107.2.1. THERE ARE STILL SECTIONS OF THE
 SANITARY RISERS THAT ARE INCOMPLETE ( LINES JUST
 BEGINNING AND ENDING WITH NO CONTINUATION POINTS
 SHOWN.)
 20) SHEET P5. 204 & P5.205 - THE FLOOR DRAINS (FD-1)
 CONNECTED TO THE OIL/WATER SEPARATOR ARE NOT
 VENTED.2014 FBC-PLUMBING SEC.901.2.1.
 21) SHTS.P5.301 & P5.302- IDENTIFY THE
 TERMINATION/CONTINUATION POINT FOR THE 24 INCH STORM
 DRAINS.
 22) SHT. P5.302 - SUBMIT AN EXPANDED RISER FOR THE
 STORM DRAINAGE. IT IS EXTREMELY DIFFICULT TO PERFORM A
 COMPREHENSIVE REVIEW ON THE CURRENT RISER. CLEARLY SHOW
 THE OVERFLOW DRAINS AND SIZES.WPB AMEND. TO FBC SEC.
 107.2.1.
 23) THE PLAN VIEW DRAWINNGS FOR THE STORM DRAINAGE ARE
 IDENTIFIED BY SECTORS AND THE STORM DRAIN RISERS ARE
 IDENTIFIED AS NORTH & SOUTH ( POINTS OF COMPASS) AND SO
 ARE THE SANITARY PLAN VIEW DRAWINGS AND RISERS. IF
 POSSIBLE, LIST THE SECTORS ON THE RISER DIAGRAMS THAT
 ARE AFFECTED BY EACH RISER. IT IS EXTREMELY DIFFICULT
 TO LOCATE THE AREAS ON THE RISERS.WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 **NOTE: DUE TO THE SANITARY RISERS BEING INCOMPLETE AND
 THE STORM DRAIN RISERS BEING DIFFICULT TO REVIEW AND
 OTHER DEFICIENCIES, A THOROUGH REVIEW COULD NOT BE
 ACCOMPLISHED AND THEREFORE MAY RESULT IN ADDITIONAL
 COMMENTS BEING GENERATED UPON RE-SUBMITTAL AND
 RE-REVIEW OF THE REVISED PLANS. DUE TO THE TIME
 SENSITIVITY OF THIS PROJECT, A MEETING WITH ME TO
 REVIEW THE DEFICIENCIES MAY BE IN THE BEST INTEREST TO
 ALL PARTIES INVOLVED.
  
 THESE COMMENTS ARE NOT ALL INCLUSIVE OF ALL OF THE
 DEFICIENCIES OF THESE PLANS, BUT ONLY FOR THE
 INFRASTRUCTURE. ADDITTIONAL PLAN REVIEW COMMENTS WILL
 BE GENERATED AT THE NEXT REVIEW DUE TO THE
 INCOMPLETENESS OF THE DRAWINGS.
  