| Date |
Text |
| 2015-12-12 13:31:26 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100870 STADIUM, NATIONAL CLUBHOUSE |
| | 15100871 ASTROS CLUBHOUSE |
| | 15100834 TEAM/ STORAGE/ BAR |
| | 15100808 SOUTH OBSERVATION TOWER |
| | 15100826 NORTH OBSERVATION TOWER |
| | |
| | ADD: 5444 N. HAVERHILL RD. |
| | CONT: HUNT CONSTRUCTION |
| | TEL: (561)568-8045 / MICHAEL SANCHEZ |
| | E-MAIL: [email protected] |
| | |
| | HCS ARCHITECT/ INTERIOR DESIGNER |
| | |
| | ASSOCIATE ARCHITECT/ INTERIOR DESIGNER |
| | GLIDDEN SPINA INTERIORS |
| | |
| | STRUCTURAL ENGINEER |
| | BLISS & NYITRAY, INC |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: SAT. OCT. 31/2015 |
| | ACTION: DENIED |
| | |
| | 1) NOTICE!!! NO RESPONSE NECESSARY. THIS PERMIT IS A |
| | STRUCTURE ONLY PERMIT, (SHELL) AND IS A PHASED PERMIT. |
| | 2014 FLORIDA BUILDING CODE WITH 2014 WEST PALM BEACH |
| | AMENDMENTS 107.3.3 PHASED APPROVAL. THE HOLDER OF SUCH |
| | PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING |
| | (STRUCTURE ONLY) SHALL PROCEED AT THE HOLDERS? OWN RISK |
| | WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT |
| | A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED. |
| | |
| | 2) PLEASE NOTE THIS PROJECT WILL REQUIRE A THRESHOLD |
| | INSPECTOR PLEASE SEE FLORIDA STATUTE FL S. S. 553.71(7) |
| | ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) COMPLIED. SHEET 0552_S0.02. 109.3.6.1 THRESHOLD |
| | INSPECTION PLAN. |
| | |
| | 2B) COMPLIED. THRESHOLD INSPECTOR FORMS. |
| | |
| | 2C) COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 110.3.7.4.4 |
| | |
| | 2D) ) COMPLIED. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME'. |
| | |
| | 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 2F) PROVISO: NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS |
| | ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | |
| | 2G) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACH?S |
| | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| | FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3-4) COMPLIED. |
| | |
| | 5) PROVISO: DEFERRED SUBMITTALS. COMPONENTS & CLADDING |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES ROOF TOP CURBS, |
| | ROOF TOP EXHAUST FANS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 6) PROVISO107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 7-25) COMPLIED. |
| | |
| | 26A) PROVISO: TO BE PART OF THE MAIN BUILDING PERMIT OR |
| | REVISION TO SHELL. CONCERN IN ROOF FRAMING PLANS, |
| | 0584_S2.131 THROUGH 0594_S2.145 THE PLANS SHOW NO |
| | THROUGH PENETRATIONS OF THE ROOF FRAMING WHERE ROOF TOP |
| | RTU UNITS WILL BE LOCATED. SHEET 0629_S7.33 ROOF |
| | FRAMING PLAN DOES SHOW A LATERAL BRACING LARGE |
| | OPENINGS. THERE WERE NO MECHANICAL SHEETS SUBMITTED FOR |
| | ROOF TOPS TO DETERMINE IF THERE ARE IN FACT ROOF TOP |
| | RTU UNITS ON THE ROOF TOP. THE ISSUE IS IF THERE ARE |
| | UNITS ADDITIONAL BRACING BETWEEN THE BAR JOIST, |
| | ATTACHMENT OF CURB TO THE MWFRS (MAIN WIND FORCE |
| | RESISTING SYSTEM). |
| | |
| | 26B) COMPLIED. THE ROOFTOP SCREENING FRAMING BE |
| | ANCHORED TO THE MWFRS (MAIN WIND FORCE RESISTING |
| | SYSTEM). 2014 FBC-B 1509.6 MECHANICAL EQUIPMENT |
| | SCREENS. |
| | |
| | 26C) PROVISO: TO BE PART OF THE MAIN BUILDING PERMIT. |
| | SHOW COMPLIANCE WITH: 2014 FBC-B WHERE EQUIPMENT AND |
| | APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR |
| | ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 |
| | MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT |
| | APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE |
| | FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND |
| | APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT |
| | REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 |
| | INCHES (762 MM) HIGH. |
| | |
| | 27) COMPLIED. |
| | |
| | 28) PROVISO: SHEET 0599_S2.511 & 0560_S2.512. BOTH |
| | THESE SHEETS INDICATE THESE BUILDINGS ARE TO BE |
| | PRE-ENGINEERED METAL BUILDINGS BY A DELEGATE ENGINEER. |
| | |
| | 29-30) COMPLIED. REMOVED FROM THIS PORTION OF PROJECT. |
| | |
| | 31) COMPLIED. STEEL EMBED PLATE/ NELSON BOLT. |
| | |
| | 32) COMPLIED) SHEET 0602_S2.612 DIRT BIN & GAS STORAGE |
| | STRUCTURE. SEPARATE PERMIT REQUIRED. |
| | 1,000 GALLON TANK |
| | 500 GALLONS GASOLINE |
| | 500 GALLONS DIESEL FUEL |
| | TANK SPECIFICATIONS UL 2085 |
| | FIRE GUARD TANK/ DOUBLE HULL W/ SECONDARY CONTAINMENT. |
| | |
| | 33) COMPLIED. NO FERTILIZERS TO BE STORED IN DIRT BIN |
| | /GAS STORAGE STRUCTURE. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |