Plan Review Notes
Plan Review Notes For Permit 15100870
Permit Number 15100870
Review Stop B
Sequence Number 2
Notes
Date Text
2015-12-12 13:31:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100870 STADIUM, NATIONAL CLUBHOUSE
 15100871 ASTROS CLUBHOUSE
 15100834 TEAM/ STORAGE/ BAR
 15100808 SOUTH OBSERVATION TOWER
 15100826 NORTH OBSERVATION TOWER
  
 ADD: 5444 N. HAVERHILL RD.
 CONT: HUNT CONSTRUCTION
 TEL: (561)568-8045 / MICHAEL SANCHEZ
 E-MAIL: [email protected]
  
 HCS ARCHITECT/ INTERIOR DESIGNER
  
 ASSOCIATE ARCHITECT/ INTERIOR DESIGNER
 GLIDDEN SPINA INTERIORS
  
 STRUCTURAL ENGINEER
 BLISS & NYITRAY, INC
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SAT. OCT. 31/2015
 ACTION: DENIED
  
 1) NOTICE!!! NO RESPONSE NECESSARY. THIS PERMIT IS A
 STRUCTURE ONLY PERMIT, (SHELL) AND IS A PHASED PERMIT.
 2014 FLORIDA BUILDING CODE WITH 2014 WEST PALM BEACH
 AMENDMENTS 107.3.3 PHASED APPROVAL. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 (STRUCTURE ONLY) SHALL PROCEED AT THE HOLDERS? OWN RISK
 WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT
 A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
  
 2) PLEASE NOTE THIS PROJECT WILL REQUIRE A THRESHOLD
 INSPECTOR PLEASE SEE FLORIDA STATUTE FL S. S. 553.71(7)
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) COMPLIED. SHEET 0552_S0.02. 109.3.6.1 THRESHOLD
 INSPECTION PLAN.
  
 2B) COMPLIED. THRESHOLD INSPECTOR FORMS.
  
 2C) COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4
  
 2D) ) COMPLIED. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME'.
  
 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) PROVISO: NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS
 ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 2G) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACH?S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3-4) COMPLIED.
  
 5) PROVISO: DEFERRED SUBMITTALS. COMPONENTS & CLADDING
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES ROOF TOP CURBS,
 ROOF TOP EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 6) PROVISO107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7-25) COMPLIED.
  
 26A) PROVISO: TO BE PART OF THE MAIN BUILDING PERMIT OR
 REVISION TO SHELL. CONCERN IN ROOF FRAMING PLANS,
 0584_S2.131 THROUGH 0594_S2.145 THE PLANS SHOW NO
 THROUGH PENETRATIONS OF THE ROOF FRAMING WHERE ROOF TOP
 RTU UNITS WILL BE LOCATED. SHEET 0629_S7.33 ROOF
 FRAMING PLAN DOES SHOW A LATERAL BRACING LARGE
 OPENINGS. THERE WERE NO MECHANICAL SHEETS SUBMITTED FOR
 ROOF TOPS TO DETERMINE IF THERE ARE IN FACT ROOF TOP
 RTU UNITS ON THE ROOF TOP. THE ISSUE IS IF THERE ARE
 UNITS ADDITIONAL BRACING BETWEEN THE BAR JOIST,
 ATTACHMENT OF CURB TO THE MWFRS (MAIN WIND FORCE
 RESISTING SYSTEM).
  
 26B) COMPLIED. THE ROOFTOP SCREENING FRAMING BE
 ANCHORED TO THE MWFRS (MAIN WIND FORCE RESISTING
 SYSTEM). 2014 FBC-B 1509.6 MECHANICAL EQUIPMENT
 SCREENS.
  
 26C) PROVISO: TO BE PART OF THE MAIN BUILDING PERMIT.
 SHOW COMPLIANCE WITH: 2014 FBC-B WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877
 MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT
 APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE
 FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) HIGH.
  
 27) COMPLIED.
  
 28) PROVISO: SHEET 0599_S2.511 & 0560_S2.512. BOTH
 THESE SHEETS INDICATE THESE BUILDINGS ARE TO BE
 PRE-ENGINEERED METAL BUILDINGS BY A DELEGATE ENGINEER.
  
 29-30) COMPLIED. REMOVED FROM THIS PORTION OF PROJECT.
  
 31) COMPLIED. STEEL EMBED PLATE/ NELSON BOLT.
  
 32) COMPLIED) SHEET 0602_S2.612 DIRT BIN & GAS STORAGE
 STRUCTURE. SEPARATE PERMIT REQUIRED.
 1,000 GALLON TANK
 500 GALLONS GASOLINE
 500 GALLONS DIESEL FUEL
 TANK SPECIFICATIONS UL 2085
 FIRE GUARD TANK/ DOUBLE HULL W/ SECONDARY CONTAINMENT.
  
 33) COMPLIED. NO FERTILIZERS TO BE STORED IN DIRT BIN
 /GAS STORAGE STRUCTURE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  