| 2016-05-12 16:58:46 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100827 |
| | ADD: 111 S. SAPODILLA AVE. |
| | CONT: THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: THURS. MAY 12/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET G.01/ COVERSHEET: |
| | |
| | 1A-D) COMPLIED |
| | |
| | 1E) 2ND REQUEST. SHEET G.01/ COVERSHEET NOR SHEET A100 |
| | THE SITE PLAN SHOW AN ASSUMED PROPERTY LINE TO THE EAST |
| | OR WEST OF THE BUILDING FOR FIRE RESISTANCE RATING |
| | REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE |
| | SEPARATION FBC-B TABLE 601 & ALLOWABLE OPENINGS FOR |
| | UNPROTECTED, NON-SPRINKLERED BUILDINGS FBC-B TABLE |
| | 705.8 . |
| | 406.5.6 FIRE SEPARATION DISTANCE. EXTERIOR WALLS AND |
| | OPENINGS IN EXTERIOR WALLS SHALL COMPLY WITH TABLES 601 |
| | AND 602. THE DISTANCE TO AN ADJACENT LOT LINE SHALL BE |
| | DETERMINED IN ACCORDANCE WITH TABLE 602 AND SECTION |
| | 705. |
| | |
| | 2) THIS BUILDING IS A 4 STORY/ 4 TIER BUILDING. |
| | THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| | THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) COMPLIED. THRESHOLD INSPECTION FORMS. |
| | |
| | 2C)COMPLIED. FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. |
| | |
| | 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION |
| | |
| | 2F) COMPLIED. 3 SETS OF DOCUMENTS. |
| | |
| | 2G) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM |
| | BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN |
| | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 2H) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| | THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 3) COMPLIED. 2014 FBC-B 406.5.8 STANDPIPE SYSTEM |
| | |
| | 4-6) COMPLIED |
| | |
| | 7) 2ND REQUEST. RESPONSE INDICATES SEE SHEET S.002 |
| | SPECS 13-31-36 FOR FABRIC AWNINGS. THE HEADING 13-31 |
| | (1) (A-F) ARE REQUIRED SHOP DRAWINGS, FABRIC AWNINGS |
| | WERE NOT INCLUDED IN THIS LIST. |
| | SHEET AP.46 DETAIL # 2,3 & 4 SHOWS AWNINGS, THERE IS NO |
| | DETAIL AS TO MATERIAL AND OR FRAMEWORK FOR THE AWNINGS |
| | NOR WIND DESIGN CRITERIA? 2014 FBC-B FABRIC AWNINGS IN |
| | COMPLIANCE WITH 3105.4 OR RIGID AWNINGS IN COMPLIANCE |
| | WITH 3105.5? |
| | |
| | 8) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2010 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. SWING & OVERHEAD GARAGE DOOR. |
| | (C) WALL LOUVERS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 9) BUILDING PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |