| Plan Review Notes For Permit 15100827 |
| Permit Number |
15100827 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-04 15:35:54 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100827 | | | 11/4/2015 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | DUCTLESS SPLIT SYSTEMS IN THE 1ST FLOOR ELECTRIC ROOM, | | | AND THE 4TH FLOOR ELEVATOR MACHINE ROOM- SEE SECTION | | | C403.2.1 FBC-14 ENERGY CONSERVATION. | | | 2) SHEET MP-101 & MP-102: INDICATE HOW THE 2ND AND 3RD | | | FLOOR UNIDENTIFIED ROOMS ADJACENT TO THE ELEVATOR ARE | | | BEING VENTILATED. THE DRAWINGS INDICATE DOORWAYS AND | | | SOME TYPE OF EQUIPMENT IN THE ROOMS WHICH IS ALSO | | | UNIDENTIFIED: PLEASE CLARIFY. | | | 3) ENERGY CALCULATIONS ARE REQUIRED PER SECTION C101.2 | | | FBC-14 ENERGY CONSERVATION. SEE SECTION C101.5 AND | | | SUBMIT THE COMPLIANCE DOCUMENTS. | | | 4) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR | | | THE CONDENSERS INSTALLED IN THE OPEN GARAGE IN | | | COMPLIANCE WITH SECTION 301,15. THE ENGINEER OF RECORD | | | SHALL PROVIDE THE WIND LOAD DESIGN CRITERIA, DESIGN | | | PRESSURES, AND DRAWINGS AND DETAILS FOR COMPLETE | | | INSTALLATIONS. | | | 5) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE TWO AIR | | | HANDLERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|