| 2016-01-05 14:24:25 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. THE APPLICABLE NEC (NFPA 70) FOR THIS JOB IS THE |
| | 2011 EDITION. CORRECT SHEET G01 ACCORDINGLY. |
| | 2. YOU ARE IN ESSENCE PARALLELING THE GROUNDED |
| | CONDUCTOR WITH THE ADDITION OF THE #4 IN THE SERVICE |
| | RACEWAY IN VIOLATION OF THE REQUIREMENTS STATED IN NEC |
| | 310.10(H)(2). |
| | 3. ACCORDING TO NEC 250.66 THE MINIMUM GROUNDING |
| | ELECTRODE CONDUCTOR FOR THE 4/0 SERVICE CONDUCTORS IS A |
| | #2, NOT EVEN THE #4 INDICATED. |
| | 4. PANEL GLP CKT 1 FACP SHALL COMPLY W/NEC 760.41(B). |
| | 5. THE FACP IN THE ELECTRICAL ROOM APPEARS TO BE |
| | SELF-SUPPORTING IN THE CENTER OF THE ROOM. CORRECT AS |
| | REQUIRED. |
| | 6. INSTALL THE REQUIRED EXIT LIGHTING AS INDICATED BY |
| | FBC-B SECTION 1011. |
| | 7. THE WIND LOAD RATING FOR THE LIGHTING POLES ON THE |
| | TOP FLOOR SHALL BE 170 MPH. |
| | 8. ALL FIRE ALARM WORK SHALL BE UNDER A SEPARATE PERMIT |
| | AND SUBMITTAL. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | |