| 2016-09-12 05:34:09 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100826 |
| | ADD: 5211 N. MILITARY TRL. |
| | CONT: HUNT CONSTRUCTION |
| | TEL: 917-202-9467 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 3RD REVIEW |
| | DATE: MON. SEPT. 12/ 2016 |
| | ACTION: DENIED |
| | |
| | 1)COMPLIED |
| | |
| | 2) COMPLIED. INSPECTIONS BY THRESHOLD INSPECTOR. |
| | |
| | 3) 3RD REQUEST RESPONSE INDICATES SEE STRUCTURAL |
| | COMMENT UNDER SEPARATE ATTACHMENT. |
| | SHEET 0605-2_S2616 PROVIDES NOTES WHERE TO FIND |
| | FOUNDATION SIZE AND STEEL, VERTICAL STEEL AND CORNER |
| | COLUMNS AS WELL AS THE 2ND FLOOR BEARING SLAB/ BEAM OF |
| | S6.11 DETAIL 15. JUST BELOW THAT NOTE THERE IS ANOTHER |
| | NOTE FOR DETAIL 5 S2.611 THIS SHEET AND DETAIL NOT |
| | FOUND? 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 4) 3RD REQUEST RESPONSE INDICATES SEE STRUCTURAL |
| | COMMENT UNDER SEPARATE ATTACHMENT. |
| | SHEET 0606_S4-11 THE MASONRY WALL SCHEDULE DOES NOT |
| | GIVE DIRECTION AS TO WHAT TO DO WITH DOOR HEADERS IN |
| | BEARING AND NON-BEARING MASONRY WALLS? WILL THERE BE |
| | DROPPED BEAMS WITH STEEL, LINTELS ETC. THERE IS NO |
| | MENTION OF FILLED CELLS & VERTICAL STEEL ON EACH SIDE |
| | OF DOOR OPENINGS. 107.2.1.3 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 5) 3RD REQUEST RESPONSE INDICATES SEE STRUCTURAL |
| | COMMENT UNDER SEPARATE ATTACHMENT |
| | PLEASE PROVIDE WHERE THE DETAILS FOR THE CONCRETE |
| | STRUCTURAL STAIRS CAN BE FOUND. SHEET 0616_S5-21 DETAIL |
| | 11 SHOWS STAIRS ON GRADE? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 6)SEMI- COMPLIED. THE FIRE PLAN REVIEWER HAS BROUGHT UP |
| | A POINT THAT THE EXTERIOR STAIR STILL NEEDS TO BE |
| | PROTECTED IN COMPLIANCE WITH 1026.6. |
| | |
| | 2ND REVIEW COMMENTS. SHEET 0333-1_A1-45 MILB THE |
| | OBSERVATION DECK PLAN SHOWS A SECTION THROUGH THE |
| | STAIRS A1.45 DETAIL 09. IN VIEWING THE OTHER DETAILS ON |
| | THIS PAGE DETAIL 07 SHOWS THE AREA BENEATH THE TO BE |
| | ENCLOSED WITH VINYL-COATED CHAINLINK FENCE AND A PAIR |
| | OF 3 FT. CHAINLINK DOORS. PLEASE REVIEW THE USE OF |
| | ENCLOSURES UNDER EXTERIOR STAIRS. 2014 FBC-B 1009.9.3 |
| | ENCLOSURES UNDER INTERIOR STAIRWAYS. |
| | |
| | THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES |
| | UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE |
| | PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION |
| | OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY |
| | ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED |
| | SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR |
| | ENCLOSURE. |
| | |
| | 7)BUILDING PROVISO: SEE ATTACHMENT TO PERMIT PLAN |
| | REVIEW |
| | |
| | 8-9) BUILDING PROVISO: DESIGNER OF RECORD RESPONSE |
| | FBC-B 1028.14.2. |
| | |
| | 10/12) BUILDING PROVISO: PRODUCT APPROVALS ARE |
| | SUBMITTED FOR ROOF PANEL SYSTEM AND THEY MEET THE |
| | REQUIRED PRESSURES.2014 FBC-B, 1609.6.4.4.1 COMPONENTS |
| | & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (31(D) ROOFING PRODUCTS AND ASSEMBLIES |
| | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) BUILDING PROVISO: 2014 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |