2016-07-12 13:28:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100826
 ADD: 5211 N. MILITARY TRL.
 CONT: HUNT CONSTRUCTION
 TEL: 917-202-9467
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. JULY 12/ 2016
 ACTION: DENIED
  
 1) SHEET 0004_A0-02 LIST THE BUILDING INFORMATION FOR
 THE BUILDINGS WITHIN THE STADIUM COMPLEX, WHICH IS MADE
 UP OF THE STADIUM, NATIONAL?S CLUBHOUSE, ASTOR?S
 CLUBHOUSE AND THE TEAM STORE/ BAR AND BUSINESS &
 ASSOCIATED STORAGE/ MAINTENANCE AREAS. THIS SHEET DOES
 NOT INCLUDE THE INFORMATION OF THE OBSERVATION TOWERS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP
 MINIMUM BUILDING TYPE
 BUILDING FIRE SPRINKLERED
 STANDPIPE
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 VERTICAL ACCESSIBILITY
  
 2) PLEASE RESPOND IF YOUR FIRM IS GOING TO USE THE
 THRESHOLD INSPECTION FIRM ALREADY AT THE SITE FOR THE
 STRUCTURAL INSPECTIONS, OR IF THE CITY BUILDING
 INSPECTORS WILL BE DOING THE BUILDING AND STRUCTURAL
 INSPECTIONS? IF THE THRESHOLD INSPECTOR WILL BE
 COMPLETING THE
  
 3) SHEET 0605-2_S2616 PROVIDES NOTES WHERE TO FIND
 FOUNDATION SIZE AND STEEL, VERTICAL STEEL AND CORNER
 COLUMNS AS WELL AS THE 2ND FLOOR BEARING SLAB/ BEAM OF
 S6.11 DETAIL 15. JUST BELOW THAT NOTE THERE IS ANOTHER
 NOTE FOR DETAIL 5 S2.611 THIS SHEET AND DETAIL NOT
 FOUND? 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
 4) SHEET 0606_S4-11 THE MASONRY WALL SCHEDULE DOES NOT
 GIVE DIRECTION AS TO WHAT TO DO WITH DOOR HEADERS IN
 BEARING AND NON-BEARING MASONRY WALLS? WILL THERE BE
 DROPPED BEAMS WITH STEEL, LINTELS ETC. THERE IS NO
 MENTION OF FILLED CELLS & VERTICAL STEEL ON EACH SIDE
 OF DOOR OPENINGS. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
 5) PLEASE PROVIDE WHERE THE DETAILS FOR THE CONCRETE
 STRUCTURAL STAIRS CAN BE FOUND. SHEET 0616_S5-21 DETAIL
 11 SHOWS STAIRS ON GRADE? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
 6) SHEET 0333-1_A1-45 MILB THE OBSERVATION DECK PLAN
 SHOWS A SECTION THROUGH THE STAIRS A1.45 DETAIL 09. IN
 VIEWING THE OTHER DETAILS ON THIS PAGE DETAIL 07 SHOWS
 THE AREA BENEATH THE TO BE ENCLOSED WITH VINYL-COATED
 CHAINLINK FENCE AND A PAIR OF 3 FT. CHAINLINK DOORS.
 PLEASE REVIEW THE USE OF ENCLOSURES UNDER EXTERIOR
 STAIRS. 2014 FBC-B 1009.9.3 ENCLOSURES UNDER INTERIOR
 STAIRWAYS.
 THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES
 UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR
 ENCLOSURE.
 7) SHEET 0333-1_A1-45 MILB THE OBSERVATION TOWER HAS
 NOT BEEN GIVEN A OCCUPANCY TYPE. THE SQUARE FOOTAGE OF
 THE OBSERVATION DECK 21X 27(NATIONALS) FEET = 567 SQ.
 FT. /15 = 38 OCCUPANTS, THE ASTROS 24.5X 23.33= 572 SQ.
 FT./ 15 = 39 OCCUPANTS. PLEASE NOTE AT THIS TIME IT IS
 ASSUMED THAT THE OBSERVATION TOWERS ARE OPEN TO THE
 PUBLIC FOR VIEWING MAKING HIS AN A5 OCCUPANCY WITH 38
 OR 39 OCCUPANTS. NO VERTICAL ACCESSIBILITY HAS BEEN
 PROVIDED. PLEASE REVIEW THE 2014 FBC-ACCESSIBILITY CODE
 201.1.1 VERTICAL ACCESSIBILITY AND EXCEPTIONS. NOTE
 OCCUPANCY LOADS ARE FIGURED UNDER THE 2014 FBC-B TABLE
 1004.1.2.
 8) SHEET 0333-1_A1-45 MILB THE OBSERVATION TOWER DETAIL
 # 9,& DETAIL 13 THE DETAIL SHOWS THE USE OF INSECT
 SCREEN ( DETAIL 13 INDICATES A ? HOLE IN SCREEN ? THICK
 SCREENING MATERIAL) IN ALUMINUM FRAMING, PLEASE PROVIDE
 HOW COMPLIANCE WITH 2014 FBC-B 1013.2 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INCLUDING MEZZANINES, EQUIPMENT PLATFORMS,
 STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED MORE THAN
 30 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR OR
 GRADE BELOW AT ANY POINT WITHIN 36 INCHES (914 MM)
 HORIZONTALLY TO THE EDGE OF 1013.3 HEIGHT. REQUIRED
 GUARDS SHALL NOT BE LESS THAN 42 INCHES HIGH, MEASURED
 VERTICALLY THE OPEN SIDE.
 9A) 2014 FBC-B 1013.2. GUARDS SHALL BE ADEQUATE IN
 STRENGTH AND ATTACHMENT IN ACCORDANCE WITH SECTION
 1607.8. 1607.8.1 HANDRAILS AND GUARDS. HANDRAILS AND
 GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50
 POUNDS PER LINEAR FOOT (PLF) IN ACCORDANCE WITH SECTION
 4.5.1 OF ASCE 7.
 9B)1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND GUARDS
 SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED LOAD OF
 200 LBS. IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7.
 9C) 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE RAILS
 (ALL THOSE EXCEPT THE HANDRAIL), BALUSTERS AND PANEL
 FILLERS SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD
 OF 50 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE
 7.
 10) SHEET 0605-2_S2-616 THE ROOF DETAIL INDICATES A
 SECTION THROUGH THE ROOF ON SHEET S2.611 DETAIL # 4.
 THIS SHEET NOT INCLUDED IN THIS SET OF PLANS. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
 11) SHEET 0551_S0.01 THE WIND DESIGN IS GIVEN FOR THE
 MAIN STADIUM FACILITY FOR A BUILDING RISK CATEGORY III.
 VULT OF 180 MPH. IS THIS SAME WIND DESIGN GOING TO BE
 USED FOR THE 2 OBSERVATION TOWERS ARE THEY TO BE
 DESIGNED AS OPEN, PARTIALLY OPEN OR ENCLOSED. PLEASE
 ALSO PROVIDE THE PRESSURES FOR ZONES 1,2,3, 4 & 5 IN
 VASD SINCE THE PRODUCT APPROVALS WILL BE IN VASD. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
 12) PLEASE SUBMIT PRODUCT APPROVALS FOR COMPLIANCE
 WITH: 2010/ 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 13) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  