| 2016-07-13 14:12:21 | 1) SHT. A0-02 - THIS SHEET DOES NOT INCLUDE THE |
| | INFORMATION FOR THE OBSERVATION TOWERS. CLARIFY. |
| | 2) INDICATE ON THE PLANS IF THESE TOWERS WILL BE OPEN |
| | TO THE VIEWING PUBLIC.IIF SO, THE TOWERS WILL BE DEEMED |
| | AN A-5 OCCUPANCY. ALSO, SUBMIT THE CORRECT OCCUPANT |
| | LOAD IF DEEMED AN A-5 OCCUPANCY.CLARIFY. |
| | 3) SHEETS C6-02 & SHT. C6-04 - THE MATCH LINES DO NOT |
| | CORRELATE WITH EACH OTHER FOR THESE TWO SHEETS. |
| | 4) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE STANDARD |
| | TOILET STALLS IN THE ASTROS AND NATIONAL RESTROOMS. |
| | COMPLY WITH 2014 FPC SEC.405.3.1. |
| | 5) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE |
| | HANDICAPPED ACCESSIBLE TOILET STALLS IN THE NATIONALS |
| | AND ASTROS RESTROOMS. |
| | 6) AT LEAST ONE LAVATORY OUTSIDE THE HANDICAPPED |
| | ACCESSIBLE STALL SHALL COMPLY WITH FAC SEC.213.3.3.4 & |
| | 606. |
| | 7) SHT. A3-23 - ACCESSIBLE STALL DETAIL SHOWS THE |
| | ACCESSIBLE STALL 7'-4" WIDE AND SHT.A1-46 SHOWS THE |
| | WIDTH AS 7"-2". CLARIFY. |
| | 8) SHT. A3-23 - ACCESSIBLE ALTERNATE ROLL-IN SHOWER |
| | DETAIL - ALTHOUGH THERE IS NO SHOWER IN THE TOWERS, |
| | THIS DETAIL IS NOT CODE COMPLIANT. PLEASE REVISE.THE |
| | GRAB BARS DO NOT COMPLY WITH THE FAC SEC.608.3.3. REFER |
| | TO FIGURE 608.3.3 IN THE FAC.GRAB BARS SHALL BE |
| | INSTALLED A MAXIMUM OF SIX INCHES FROM ADJACENT WALLS |
| | AND SHALL NOT BE PROVIDED ABOVE THE SEAT. A PORTION OF |
| | THE GRAB BAR APPEARS TO BE ABOVE THE SEAT AND IS MORE |
| | THAN SIX INCHES FROM ONE ADJACENT WALL. |
| | 9) SHT. A3-40 - ROOM FINISH SCHEDULE - SOME OF THE |
| | MEN'S & WOMEN'S RESTROOMS SHOW THE WALL FINISH AS |
| | PAINT. WALLS WITHIN TWO FEET OF WATER CLOSETS AND |
| | URINALS SHALL COMPLY WITH FFBC 2014 SEC.1210.2.2. |
| | 10) SHT.P4-000 SHOWS A FLOOR DRAIN WITHIN THE PLUMBING |
| | CHASE.THIS IS NOT PERMITTED BY SEC.412.2 OF THE 2014 |
| | FPC. READY ACCESS SHALL BE PROVIDED TO FLOOR DRAINS. |
| | RREFER TO FPC SEC.202 FOR DEFINITION OF "READY ACCESS." |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |