| 2016-09-08 11:03:02 | 5211 NORTH MILITARY - OBSERVATION TOWER | | | PERMIT #15100826 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | REPEAT COMMENTS: THE EXTERIOR STAIR IS REQUIRED TO BE | | | SEPARATED FROM THE INTERIOR OF THE BUILDING WITH A | | | 1-HOUR FIRE BARRIER AND PROTECTED OPENINGS PER NFPA 101 | | | SECTION 7.2.2.6.3.1. THE STAIRS DISCHARGE BEYOND THE | | | FACE OF THE BUILDING AND REQUIRE THE 1-HOUR FIRE | | | BARRIER TO EXTEND 10-FEET HORIZONTALLY FROM THE STAIR. | | | THIS WILL REQUIRE THE DOORS TO BE FIRE RATED AND THE | | | LOUVERS TO BE PROTECTED WITH FIRE DAMPERS. | | | | | | REPEAT COMMENT: HAZARD SEPARATION: FIELD STORAGE #02803 | | | NEEDS TO BE FIRE SEPARATED FROM THE BUSINESS OCCUPANCY | | | WITH EITHER 1-HOUR FIRE BARRIER OR FIRE SPRINKLERS PER | | | NFPA 101 SECTION 38.3.2 PROTECTION FROM HAZARDS. | | | HAZARDOUS AREAS INCLUDING, BUT NOT LIMITED TO, AREAS | | | USED FOR GENERAL STORAGE, BOILER OR FURNACE ROOMS, AND | | | MAINTENANCE SHOPS THAT INCLUDE WOODWORKING AND PAINTING | | | AREAS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION | | | 8.7. THIS IS A HAZARD SEPARATION AND NOT AN OCCUPANCY | | | SEPARATION, WHICH WOULD REQUIRE A 2-HOUR FIRE BARRIER. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|