Plan Review Notes
Plan Review Notes For Permit 15100826
Permit Number 15100826
Review Stop P
Sequence Number 1
Notes
Date Text
2015-11-03 12:38:081) SHT.A0.02 - SUBMIT INFORMATION AS TO HOW THE
 PLUMBING FIXTURE COUNT FOR ALL THE AREAS OTHER THAN THE
 CONCOURSE AND FIELD WAS CALCULATED. THE NUMBER OF
 REQUIRED PLUMBING FIXTURES ON THE CHART ON SHT.A0.02
 DOES NOT APPEAR TO CORRELATE WITH TABLE 403.1 OF 2014
 FBC-PLUMBING FOR AN A-5 OCCUPANCY AS CLASSIFIED ON THE
 PLANS. HOW DID YOU ARRIVE AT THE REQUIRED NUMBER OF
 FIXTURES?
 2) SHT.A0.02 - CLARIFY THE FOOTNOTES WITH THE SINGLE,
 DOUBLE AND TRIPLE ASTERISKS AT THE BOTTOM OF THE
 FIXTURE COUNT CHART.( THE EXCEPTION IN SEC. 410.1 IN
 THE PLUMBING CODE REGARDING THE REQUIREMENT FOR
 DRINKING FOUNTAINS APPLIES TO RESTAURANTS, AN A-2
 OCCUPANCY AND IS NOT APPLICABLE HERE .)
 3) SHT. A0.02 - CLARIFY FOOTNOTE #1 REGARDING THE
 OBSERVATION TOWER FIXTURES.
 4) PLACE A NOTE ON THE IRRIGATION PLANS THAT THE
 REQUIRED RAIN SENSORS ARE LOCATED AT THE CONTROLLERS AS
 THAT IS WHERE I ASSUME THEY WILL BE. IF NOT, SHOW THE
 LOCATION OF THE RAIN SENSORS ON THE IRRIGATION PLANS.
 FL. STATUTE 373.62.
 5) SHT. A8.11 - DETAILS #01 & #08, SHT.A8.21 - DETAIL
 #01 & SHT.A8.31 DETAIL #01 REFER TO AN OIL
 SEPARATOR.SUBMIT A DETAIL OF THE OIL INTERCEPTOR THE
 INTERCEPTOR SHALL COMPLY WITH 2014 FBC-PLUMBING
 SECS.1003.4 THRU 1003.4.2.1.
 6) LINT INTERCEPTORS SHALL COMPLY WITH 2014
 FBC-PLUMBING SEC.1003.6. PROVIDE A DETAIL AND SIZING
 CALCULATIONS FOR THE LINT INTERCEPTORS. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.
 7) SUBMIT A DETAIL AND SIZING CALCULATIONS FOR THE
 GREASE INTERCEPTORS. FACTORY SIZING CALCULATIONS DONE
 BY THE MANUFACTURER ARE REQUIRED FOR THE SIZING OF
 HYDROMECHANICAL GREASE INTERCEPTORS TO ENSURE PROPER
 SIZING.2014 FBC-PLUMBING SEC. 1003.2.
 8) PROVIDE THE PROPER MATCH LINES ON THE PLUMBING
 DRAWINGS. THERE ARE NO MATCH LINES ON THE TOP OF THE
 PAGES & SOME OF THE MATCH LINES DO NOT CORRELATE WITH
 EACH OTHER. CHECK ALL SHEETS.
 9) INDICATE THE MINIMUM PITCH OF THE HORIZONTAL STORM
 DRAINS. NOTE # 34 ON SHT. P0.01 STATES THAT ALL STORM
 MUST SLOPE A MINIMUM OF 1/8". AT AN 1/8" PITCH THERE
 ARE QUITE A FEW AREAS THAT THE PIPE IS UNDERSIZED. TO
 COMPLY WITH TABLE 1106.3 OF THE FPC THE MINIMUM PITCH
 OF SOME AREAS SHALL BE 1/4" IF NOT MORE. THE SPECIFIC
 PITCH OF THE PIPE FOR THE STORM DRAINAGE SYSTEM SHALL
 BE NOTED ON THE PLANS FOR THE SQUARE FOOTAGE .WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) PLUMBING UNDERSLAB DRAWINGS - THESE DRAWINGS ARE
 SEVERELY INCOMPLETE AND A THOROUGH AND COMPREHENSIVE
 REVIEW COULD NOT BE PERFORMED. THERE ARE STORM AND
 SANITARY LINES THAT START AND STOP AND GO NOWHERE, DO
 NOT SHOW CONTINUATION POINTS, PIPE SIZES DO NOT MATCH
 BETWEEN PLANS, PIPE SIZES ARE SHOWN AND THERE IS NO
 PIPE AND IS IMPOSSIBLE TO FIGURE OUT WHAT IS GOING
 WHERE IN AREAS.THERE ARE JUST TOO MANY DEFICIENCIES TO
 LIST.SUBMIT 100% COMPLETE UNDERSLAB DRAWINGS FOR
 REVIEW.WPB AMEND. TO 2014 FBC SEC. 107.2.1,
 107.3.5.1.3.
 11) SANITARY RISER DRAWINGS. SEE THE COMMENT FOR THE
 UNDERSLAB DRAWINGS. PIPE SIZES ARE MISSING, VENTS ARE
 MISSING, FIXTURES ARE NOT IDENTIFIED, PIPES GO NOWHERE,
 ETC., ETC.LOOK AT THE DRAWINGS AND YOU WILL SEE THE
 ENORMOUS DEFICIENCIES.THERE ARE TOO MANY TO LIST.THE
 DRAWINGS ARE SEVERELY INCOMPLETE AND A THOROUGH AND
 COMPREHENSIVE REVIEW COULD NOT BE PERFORMED. SUBMIT
 100% COMPLETE RISER DIAGRAMS FOR REVIEW. WPB AMEND. TO
 2014 FBC SEC. 107.2.1, 107.3.5.1.3.
 12) SHT. P5.301 - NOTE # 5 - IT APPEARS THE VERTICAL
 LEADERS AND CONDUCTORS HAVE BEEN SIZED IN ACCORDANCE
 WITH TABLE 1106.3 OF THE FLORIDA PLUMBING CODE BASED ON
 THE SQUARE FOOTAGE LISTED WHICH APPLIES TO HORIZONTAL
 STORM DRAIN PIPING.TABLE 1106.2 (1) MAY BE USED FOR
 SIZING VERTICAL CONDUCTORS AND LEADERS. JUST AN FYI.
 13) STORM DRAINAGE DRAWINGS - SHTS.P5.301 & P5.302 -
 PIPE SIZES MISSING, RISERS NOT IDENTIFIED, INCORRECT
 SIZING, INCOMPLETE PLANS, NO DETAILS FOR INTERCEPTORS,
 NO RISER DIAGRAM FOR OVERFLOW DRAINAGE SYSTEM, ETC.,
 ETC.. AGAIN, THESE DRAWINGS ARE SEVERELY INCOMPLETE AND
 A THOROUGH AND COMPREHENSIVE PLAN REVIEW COULD NOT BE
 PERFORMED. SUBMIT 100 % COMPLETE STORM DRAINAGE PLANS
 FOR REVIEW. WPB AMEND. TO 2014 FBC SEC. 107.2.1,
 107.3.5.1.3.
 14) LIST THE SPECIFIC SHEET NUMBER WHERE A NOTE STATES
 " SEE CIVIL DRAWINGS FOR CONTINUATION." OR "SEE
 ARCHITECTURAL DRAWINGS." WPB AMEND. TO FBC SEC.
 107.2.1.
 15) SHT. P6.01 - NOTE #4 STATES THAT ALARMS ARE
 OPTIONAL ON THE STANCOR SYSTEM.WILL THIS SYSTEM BE USED
 IN LIEU OF AN OIL SEPARATOR? IF SO, AN APPROVED ALARM
 SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH 2014 FPC
 SEC.1003.4 EXCEPTION. CLARIFY. IF THE STANCOR SYSTEM IS
 BEING USED SUBMIT THE MANUFACTURER'S SPECIFICATION
 SHEETS FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 16) SHT. H1.00 - SEC. 1.02 - REQUIREMENTS - DELETE THE
 REFERENCE TO THE INTERNATIONAL BUILDING CODE AND INSERT
 THE 2014 FLORIDA BUILDING CODE.
 17) SUBMIT THE SITE DRAINAGE PLANS FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1.
 18) SUBMIT A DETAIL FOR THE ROOF AND OVERFLOW DRAINS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 19) ALL DOWNSPOUTS DISCHARGING TO THE GROUND SHALL
 DISCHARGE A MINIMUM OF ONE FOOT FROM THE BUILDING WALL
 PER THE 2014 FBC SEC.1503.7.
 20) THE MINIMUM RAINFALL RATE THAT THE STORM DRAINAGE
 SYSTEM SHALL BE DESIGNED ON IS 5 INCHES PER 2014
 FBC-PLUMBING SEC. 1106.1. ( THERE IS NO 4.5 INCH
 RAINFALL RATE LISTED IN THE SIZING TABLES.)
  
 THESE COMMENTS ARE NOT ALL INCLUSIVE OF ALL OF THE
 DEFICIENCIES OF THESE PLANS, BUT ONLY FOR THE
 INFRASTRUCTURE. ADDITTIONAL PLAN REVIEW COMMENTS WILL
 BE GENERATED AT THE NEXT REVIEW DUE TO THE
 INCOMPLETENESS OF THE DRAWINGS.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  